VENTING AND INSTALLATION

1. Heat -N-Glo gas inserts are designed for recessed installations into solid fuel

Masonry or Factory Built Non Combustible fireplaces that have been installed

in accordance with the National, Provincial, State and local building codes.

2. Minimum fireplace opening requirements are shown in Figure 1 of this instal-

lation manual. The firebrick (refactory) can be removed from a factory built

fireplace in order to gain minimum gas insert opening requirements.

3. To assure top performance, safety and efficiency, inserts must be installed

with an approved flue liner as per CAN/CGA B-149 or National Fuel Code

ANSI Z223 and these instructions.

WARNING

THE SOLID FUEL FIREPLACE HAS BEEN CONVERTED FOR USE

WITH GAS ONLY AND CANNOT BE USED FOR BURNING WOOD

OR SOLID FUELS UNLESS ALL ORIGINAL PARTS HAVE BEEN

REPLACED AND THE FIREPLACE HAS BEEN REAPPROVED BY

THE AUTHORITY HAVING JURISDICTION.

4. The solid fuel fireplace’s flue damper must be fully locked in the open position

or removed for installation.

5. The chimney must be cleaned and in good working order and constructed of

noncombustible materials.

6. Make sure that all chimney cleanouts fit properly so air cannot leak into the

chimney.

7. Install the insert without the trim surround and make all gas, venting, and

electrical connections.

WARNING

Under no circumstances cutting of sheet metal surfaces are al-

lowed for installation.

If the factory built fireplace has no gas access holes provided, an

access hole of 1” diameter (25mm) or less may be drilled through

the lower sides or bottom of the combustion chamber in a proper

workmanship like manner.

8. Install decorative trim surround. Please refer to instructions included with the

trim surround.

Ensure there are no obstructions to side air passages of decora-

tive trim once installed on insert.

!

!

!

!