4.7.1 Sub-function codes supported
Only Sub-function 00 is supported by the MNET gateway.
The data passed in the request data field is to be returned (looped back) in the
response. The entire response message should be identical to the request.
00 Return Query Data
Sub-function
Data Field (Request)
Data Field (Response)
00 00
Any
Echo Request Data
Here is an example of a request to remote device to Return Query Data. This
uses a sub-function code of zero (00 00 hex in the two-byte field). The data to be
returned is sent in the two-byte data field (A5 37 hex).
Example and state diagram
Request
Response
Field Name
(Hex)
Field Name
(Hex)
Function
08
Function
08
Sub-function Hi
00
Sub-function Hi
00
Sub-function Lo
00
Sub-function Lo
00
Data Hi
A5
Data Hi
A5
Data Lo
37
Data Lo
27
The data fields in responses to other kinds of queries could contain error counts
or other data requested by the sub-function code.
- 5201-MNET-DFCM 5208-MNET-HART 5303-MBP-MNET 5204SE-MNET-PDPMV1 5202-MNET-ADM4 5201-MNET-BACNET 5210-MNET-RIO 5228-MNET-HART 5207-MNET-HART 5205-MNET-PDPS 5204-MNET-PDPMV1 5201-MNET-DH485 5201-MNET-104S 5201-MNET-EGD 5201-MNET-DFNT 5201-MNET-DNPSNET 5201-MNET-103M 5201-MNET-101S 5201-MNET-DNPS 5201-MNET-DNPM 5202-MNET-DFCM4 5202-MNET-ASCII4