4.2

Areas in Special Module

Communication

address

Devices

Attribute

Data type

Length

H’1600 ~ H’1630

1

st

special module: CR0 ~ CR48

word

49

H’1640 ~ H’1670

2

nd

special module: CR0 ~ CR48

word

49

H’1680 ~ H’16B0

3

rd

special module: CR0 ~ CR48

word

49

H’16C0 ~ H’16F0

4

th

special module: CR0 ~ CR48

word

49

H’1700 ~ H’1730

5

th

special module: CR0 ~ CR48

word

49

H’1740 ~ H’1770

6

th

special module: CR0 ~ CR48

word

49

H’1780 ~ H’17B0

7

th

special module: CR0 ~ CR48

word

49

H’17C0 ~ H’17F0

8

th

special module: CR0 ~ CR48

Please refer to
theCR attribute of
each special
module.

word 49

Note:

Maximum 8 special modules are connectible to RTU-485. The first special module connected is the nearestone

on the right hand side of RTU-485, and so on.

4.3 Special

Functions

Communication

address

Attribute

Content

Explanation

H’0000 R

Model

name

Set up by the system. Model code of RTU-485 =
H’0200.

H’0001 R

Firmware

version

The current firmware version is displayed in hex,
e.g. V0.1 is indicated as H’0010.

H’0002 R

Issue

date

The issue data of the firmware is displayed in
hex, e.g. H’1FD0 = K8150 indicates that the
firmware is issued on the morning of August 15.

H’0003 R/W

RUN/STOP

RTU-485

H’0003 = K1, RTU-485 RUN;

H’0003 = K0, RTU-485 STOP.

H’0004 R

Communication

format

Displaying the communication format of
RTU-485.

H’0005

R

Baud rate

Displaying the baud rate of RTU-485.

H’0006 R

Communication
address

Displaying the communication address of
RTU-485.

H’0007 R

Number of DI/DO
points

High byte stores the number of input points. Low
byte stores the number of output points.

H’0008 R

Error

code

Recording the current error. See 17.4.4 for the
meaing of error codes.

H’0009

R

Historical error code

The number of errors occurring.

Range: 0 ~ 32

H’0017 R

Number of special
modules

The number of special modules RTU-485
detects.

H’0018 R

Model code of the 1

st

special module

The model code of the 1

st

special module

connected to RTU-485.

H’0019 R

Model code of the 2

nd

special module

The model code of the 2

nd

special module

connected to RTU-485.

H’001A R

Model code of the 3

rd

special module

The model code of the 3

rd

special module

connected to RTU-485.

H’001B R

Model code of the 4

th

special module

The model code of the 4

th

special module

connected to RTU-485.