Modbus Remote I/O Communication Module RTU-485

DVP-PLC Application Manual

3

1 Introduction

1. To ensure correct installation and operation of RTU-485, please read this chapter carefully before using your

RTU-485

2. RTU-485 is a Modbus remote I/O communication module for Delta’s PLC to remote-control DVP Slim series

DI/DO and AI/AO extension modules.

3. RTU-485 is a standard Modbus slave device and is compatible with pther master devices which comply with

Modbus protocol.

1.1 Features

y

Auto-detecting extension modules

y

Maximum extension: 8 special modules; 128 input points and 128 output points

1.2 Specifications

ƒ DeviceNet connection

Transmission method

RS-485

Electrical isolation

500 VDC

Interface Removable

connector

(3Pin)

Transmission cable

2-wire twister shielded cablew8

ƒ Communication

7, E, 1

7, O, 2

8, O, 1

7, O, 1

7, N, 2

8, N, 1

ASCII

7, E, 2

8, E, 1

8, N, 2

Mode

RTU

8, E, 1

8, O, 1

8, N, 1

8, N, 2

Baud rates

1,200bps; 2,400bps; 4,800bps; 9,600bps; 19,200bps; 38,400bps;
57,600bps; 115,200bps

ƒ

Electrical

specification

Power supply

24 VDC (-15% ~ 20%) (with DC input polarity reverse protection)

ƒ Environment

Noise immunity

ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge,4KV Contact
Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV
Analog & Communication I/O: 1KV
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS (IEC 61131-2, IEC 61000-4-3): 80MHz~1000MHz , 1.4GHz~2.0GHz ,
10V/m

Operation

0ºC ~ 55ºC (temperature); 50 ~ 95% (humidity); pollution degree 2

Storage

-25ºC ~ 70ºC (temperature); 5 ~ 95% (humidity)

Vibration/shock
resistance

Standard: IEC 61131-2、IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27
(TEST Ea)

Certificates

IEC 61131-2, UL508