Repair Section

97

11. REASSEMBLY

11.1 Removal of Unit

• Reassemble the unit in the reverse order of removal. Described below are the parts that require

special care in reassembling the unit. Perform all wiring or rewiring as referenced in the wiring
diagram.

11.2 Compressor Mounting

• Mount the compressor on the frame, using

cushions, steel collars, plate washers and nuts.

11.3 Blower Assembly

Tighten the set screws of indoor and outdoor fans

at the torque shown below.

CAUTION

• Tightening torque:

- 10.84 ± 2.17 ft•lbf (15 ± 2.7 N•m)

11.4 Wiring Notice

• Secure the wires using clamps so that they do not come into contact with the edges of the

structure. Secure the wires using clamps in the same position they were before removal.

ILL00178-00

Nut

Steel Collar

Cushion

Plate Washer

ILL00913-00

Set Screw