Error handling and diagnostics
Embedded PC
49
....
IF k_bus_state = 1
THEN
(* an error occured on K-Bus*)
k_bus_request := TRUE;
(* request vaules for ErrCode and ErrArg *)
CASE k_bus_err_code OF
0 : return;
(* should not happen, though an error occured *)
1 : CASE k_bus_arg OF
0 : report error;
(* EEPROM checksum error *)
1 : report error;
(* overflow in code buffer *)
2 : report error;
(* unknown datatype *)
END_CASE;
2 : CASE k_bus_arg OF
0 : report error;
(* programmed configuration, wrong table entry *)
ELSE report error;
(* wrong table entry *)
END_CASE;
3 : report error
(* K-Bus command error *)
4 : CASE k_bus_arg OF
0 : report error;
(* break after power supply *)
ELSE report error;
(* break after terminal 'k_bus_arg' *)
END_CASE;
5 : report error
(* K-Bus-error during register-communication with
terminal 'k_bus_arg' *)
9 : CASE k_bus_arg OF
0 : report error;
(* checksum error in program flash *)
ELSE report error;
(* terminal 'k_bus_arg' does not exist in boot
configuration *)
END_CASE;
14 : report error
(* 'k_bus_arg'-th terminal has wrong format *)
15 : report error
(* wrong number of bus terminals *)
16 : report error
(* length of K-Bus data is invalid *)
END_CASE
k_bus_request := TRUE;
(* reset bus, if reason for error is removed, bus
starts again *)
....
To make the control work, the register and the program must be linked in System Manager. If the PLC program is
attached in System Manager the following signals are available: