Important: t, Only – Interlogix NX-1710E Addendum User Manual
Page 2
Tip:
Defaults are shown in bold italics.
L
OCATION
54
WEIGAND FORMAT 1 – P
ARITY
T
YPE
4
(1 segment of decimal data) This location programs the Partity Type 4 for Weigand Format 1. Available options for this location are 0 = No Parity; 1 = Odd Parity; 2 = Even Parity.
Factory default is 0.
L
OCATION
55
WEIGAND FORMAT 1 – P
ARITY
M
ASK
4
(8 segments of binary data) This location tells which bits to include for the parity count; and includes the parity bits. It is used in conjunction with Location 54 (Parity Type 4). The factory
default is:
Seg 1
Seg 2
Seg 3
Seg 4
Seg 5
Seg 6
Seg 7
Seg 8
--------
--------
--------
--------
-------- -------- -------- --------
L
OCATION
56
WEIGAND FORMAT 1 – P
ARITY
T
YPE
5
(1 segment of decimal data) This location programs the Partity Type 5 for Weigand Format 1. Available options for this location are 0 = No Parity; 1 = Odd Parity; 2 = Even Parity.
Factory default is 0.
L
OCATION
57
WEIGAND FORMAT 1 –
P
ARITY
M
ASK
5
(8 segments of binary data) This location tells which bits to include for the parity count; and includes the parity bits. It is used in conjunction with Location 56 (Parity Type 5). The factory
default is:
Seg 1
Seg 2
Seg 3
Seg 4
Seg 5
Seg 6
Seg 7
Seg 8
--------
--------
--------
--------
-------- -------- -------- --------
L
OCATIONS
58 – 70
WEIGAND FORMAT 2
(T
ECOM
ASC 27
BIT
)
These locations contain the programming for Weigand Format 2. Refer to the instructions for Locations 45 – 57 regarding the Bit Descriptors, Parity Types and Parity Masks 1-5. Factory
defaults are in the worksheets.
L
OCATIONS
71 - 83
WEIGAND FORMAT 3
(HID1000)
L
OCATIONS
84 – 96
WEIGAND FORMAT 4
(H10304)
L
OCATIONS
97 - 109
WEIGAND FORMAT 5
(40
BIT W
/F
ACILITY CODE
–
C
ASI
4001)
L
OCATIONS
110 - 122 WEIGAND FORMAT 6
(40
BIT W
/
O
F
ACILITY CODE
–
C
ASI
4002)
L
OCATIONS
123 - 135 WEIGAND FORMAT 7
(U
NDEFINED
)
L
OCATIONS
136 - 148 WEIGAND FORMAT 8
(U
NDEFINED
)
PROGRAMMING WORKSHEETS for Locations 44 - 148
SEG
DESCRIPTION
LOCATION 44 – CODE ENTRY LOGGING PARTITION
1
Code Entry Logging Partition for Reader “A”
Default = 0
2
Code Entry Logging Partition for Reader “B”
Default = 0
IMPORTANT: T
HE FOLLOWING LOCATIONS ARE CONSIDERED ADVANCED PROGRAMMING AND SHOULD
ONLY
BE USED BY INSTALLERS WITH A THOROUGH
UNDERSTANDING OF
W
EIGAND FORMATS
.
D
O NOT ATTEMPT TO PROGRAM THESE LOCATIONS IF YOU ARE NOT FAMILIAR WITH
W
EIGAND PACKETS
.
WEIGAND FORMAT 1
LOCATION 45 – WIEGAND FORMAT 1 (DIGITS & BITS) (DECIMAL DATA)
SEG DESCRIPTION
DEFAULT
DATA
1
Number of Digits in Facility Code
5
2
Number of Digits in Badge Number
5
3
Number of Bits in Facility Code
8
4
Number of Bits in Badge Number
16
5
Total Number of Bits in Complete Weigand Format (including parity bits)
26
LOCATION 46 – WIEGAND FORMAT 1 (BIT DESCRIPTOR 1 - 32) HEX DATA
0 = Always Zero; 1 = Always One; B = Badge Number Bit; D = Parity Bit; E = End of Format; F = Facility Code Bit
SEG DESCRIPTION
DEFAULT
DATA
SEG
DESCRIPTION
DEFAULT
DATA
1
Bit 1 Descriptor
D
17
Bit 17 Descriptor
B
2
Bit 2 Descriptor
F
18
Bit 18 Descriptor
B
3
Bit 3 Descriptor
F
19
Bit 19 Descriptor
B
4
Bit 4 Descriptor
F
20
Bit 20 Descriptor
B
5
Bit 5 Descriptor
F
21
Bit 21 Descriptor
B
6
Bit 6 Descriptor
F
22
Bit 22 Descriptor
B
7
Bit 7 Descriptor
F
23
Bit 23 Descriptor
B
8
Bit 8 Descriptor
F
24
Bit 24 Descriptor
B
9
Bit 9 Descriptor
F
25
Bit 25 Descriptor
B
10 Bit 10 Descriptor
B
26
Bit 26 Descriptor
D
11 Bit 11 Descriptor
B
27
Bit 27 Descriptor
E
12 Bit 12 Descriptor
B
28
Bit 28 Descriptor
E
13 Bit 13 Descriptor
B
29
Bit 29 Descriptor
E
14 Bit 14 Descriptor
B
30
Bit 30 Descriptor
E
15 Bit 15 Descriptor
B
31
Bit 31 Descriptor
E
16 Bit 16 Descriptor
B
32
Bit 32 Descriptor
E
LOCATION 47 – WIEGAND FORMAT 1 (BIT DESCRIPTOR 33 - 64)
1
Bit 33 Descriptor
E
17
Bit 49 Descriptor
E
2
Bit 34 Descriptor
E
18
Bit 50 Descriptor
E
3
Bit 35 Descriptor
E
19
Bit 51 Descriptor
E
4
Bit 36 Descriptor
E
20
Bit 52 Descriptor
E