Sample application, Troubleshooting, Maintenance – KMC Controls REE-5501 User Manual

Page 2: Important notices

background image

REE-5001/REE-5501

2

Installation Guide

CSP–5001

Controller-Actuator

H

~

16

V

DC

I

N

O

U

T

–

–

L

24 VAC

REE–5001 Relay Module

~

–

24

V

A

C

3

2

1

Stages

3-Stage Reheat

T

Load

(To Flow Sensor)

24 VAC @ 34 VA

~

–

–

12

V

V1 T3 R1 T1

A

+

CTE–5103

T2 R2 T4 V2

REE–1005 Relay Module

Y

X

Controller

5

4

A

NC

N

O

C

Sensor

24 VAC Contactors

(10 VA Max. per Stage)

TTE–2001

Duct Sensor

1
2
3

2

1

3

Jumpers

© 2012 KMC Controls, Inc.

809-019-03G

KMC Controls, Inc.

19476 Industrial Drive

New Paris, IN 46553

574.831.5250

www.kmccontrols.com; [email protected]

Important Notices

The material in this document is for information pur-

poses only. The contents and the product it describes

are subject to change without notice. KMC Controls,

Inc. makes no representations or warranties with

respect to this document. In no event shall KMC Con-

trols, Inc. be liable for any damages, direct or incidental,

arising out of or related to the use of this document.

Heating

Max.

Heating Min.

0 fpm

(

Colder

Room Temperature

Warmer

)

3300

fpm

T2

Signal

Cooling

Max.

Cooling Min.

T1

Signal

Cooling Setpoint

Heating Setpoint

Air

Flow

9.5 V

6.5 V

3.5 V

#3

#2

#1

Reheat

Stages

T4 Signal

T4 Voltage

NOTE: Minimums must be sufficient for reheat.

Sample Application

NOTE: For more

information about

this CSP-5001 and

CTE-5103 example,

see the CSP-

5001/5002 VAV

Flow Controller-

Actuators

Application Guide.

NOTE: Triac outputs

are

for 24 VAC loads

only.

NOTE: For the REE-5001,

the phase side of

the transformer

connects to

the “common”

side of the load

(contactors)

.

Maintenance

No routine maintenance is required, however protec-

tion from extremes of humidity and dirt is recom-

mended. Careful installation will also ensure long

term reliability and performance.

Stage Status

Normal Triac Voltage (Approximate, and With Load)

Across

Load

(Terminal

~/Phase to

Terminal 1, 2, or 3)

Across

Triac

(Terminal

–/Neutral to

Terminal 1, 2, or 3)

On

24 VAC

1 VAC

Off

0 VAC

24 VAC

Troubleshooting

• Check the wiring.
• Check the voltage from the thermostat/controller

(measured from Terminal T to Terminal

–/Neutral). (See the voltage charts

above and on

the previous page.)

• Check the voltage across the triac and load. (See

the chart below.)

This manual is related to the following products: