beautypg.com

Bryant DURAPAC 580F User Manual

Page 38

background image

38

2-Row Coils (Sizes 048-073)

Clean coil as follows:

1. Turn off unit power and install lockout tag.
2. Remove top panel screws on condenser end of unit.
3. Remove condenser coil corner post. See Fig. 36. To

hold top panel open, place coil corner post between
top panel and center post. See Fig. 37.

4. Remove screws securing coil to compressor plate and

compressor access panel.

5. Remove fastener holding coil sections together at re-

turn end of condenser coil. Carefully separate the
outer coil section 3 to 4 in. from the inner coil section.
See Fig. 38.

6. Use a water hose or other suitable equipment to flush

down between the 2 coil sections to remove dirt and
debris. Clean the outer surfaces with a stiff brush in
the normal manner.

7. Secure inner and outer coil rows together with a field-

supplied fastener.

8. Reposition the outer coil section and remove the coil

corner post from between the top panel and center
post. Reinstall the coil corner post and replace all
screws.

C. Condensate Drain

Check and clean each year at start of cooling season. In win-
ter, protect condensate drain against freeze-up.

D. Filters

Clean or replace at start of each heating and cooling season,
or more often if operating conditions require it. Replacement
filters must be same dimensions as original filters.

E. Outdoor-Air Inlet Screen

Clean screen with steam or hot water and a mild detergent.
Do not use disposable filters in place of screen.

II. LUBRICATION

A. Compressors

Each compressor is charged with the correct amount of oil at
the factory.

B. Fan Motor Bearings

Fan motor bearings are of the permanently lubricated type.
No further lubrication is required. No lubrication of con-
denser or evaporator fan motors is required.

III. BLOWER BELT ADJUSTMENT

Inspect blower belt for wear, proper belt tension, and pulley
alignment as conditions require or at the beginning of each
heating and air conditioning season.

Refer to Step 9 — Adjust Evaporator-Fan Speed on page 22
for adjustment and alignment procedures.

Check belt tension at least once each heating or cooling sea-
son or as conditions require. Adjust as required.

IV. MANUAL OUTDOOR-AIR DAMPER

If outdoor-air damper blade adjustment is required, see
Manual Outdoor-Air Damper section on page 14.

Fig. 36 — Cleaning Condenser Coil

Fig. 37 — Propping Up Top Panel

Fig. 38 — Separating Coil Sections