EQUITEST

5071

EN - 37

10. TECHNICAL

SPECIFICATIONS

Accuracy indicated as [%reading + (number of digits)* resolution] at 23°C±5°C, <60%RH

Continuity of protective conductors with 200mA (LOW

)

Mode

Measuring range

(

)

Resolution (

)

Accuracy (*)

AUTO, R+TIMER, R-TIMER

0.01

 9.99

0.01

(2%rdg + 2digits)

10.0

 99.9

0.1

(*) Considering the calibration of measuring cables
Test current

>200mA DC up to 5

 (including calibration value)

Current measurement resolution

1mA ; Open-circuit voltage: 4V < V

0

< 12V

Continuity of protective conductors with 10A (LOW

10A)

Measuring range (

) Resolution

(

)

Accuracy

0.001

 0.999

0.01

(1%rdg + 2digits)

Test current

> 10A AC up to 0.45

Current measurement resolution

0.1A

Open-circuit voltage

< 12V AC

Measuring mode

4 terminals

Power supply

230V AC / 50/60Hz

Continuity of PE conductors in compliance with IEC/EN60204-1:2006 (LOW

10AE204)

Measuring range (

) Resolution

(

)

Accuracy

0.001

 0.999

0.01

(1%rdg + 2digits)

Test current

> 10A AC up to 0.45

 ; Current measure resolution: 0.1A ; Open-circuit voltage < 12V AC

Length measuring range

0.1m

 999.9m ;

Selectable section

0.5, 1, 1.5, 2.5, 4, 6, 10, 16mm

2

; Copper resistivity 0.017

mm

2

/m

Measuring mode

4 terminals

Power supply

230V AC / 50/60Hz

Contact voltage (U

t

)

Range (V)

Resolution (V)

Accuracy

0

 2U

t lim

0.1

-0%, +(10%rdg + 3digits)

U

t

lim (U

L

): 25V or 50V

Frequency

Range (Hz)

Resolution (Hz)

Accuracy

47.0

 63.6

0.1

(0.1%reading+1digit)

LOOP measurement is only active for 50Hz ±0.5Hz

AC voltage measurement (LOOP,

)

Measuring range (V)

Resolution (V)

Accuracy

15

 460

1

(3%rdg + 2digits)

Line impedance (Phase – Phase / Phase - Neutral)

Range (

) Resolution

(

) (*)

Accuracy

0.01

 9.99

0.01

(5%rdg + 3digits)

10.0

 199.9

0.1

(*) 0.1m

 in range 0.0  199.9 m (with IMP57)

Maximum peak current at test voltage: 3.65A (127V) ; 6.64A (230V) ; 11.5A (400V)

Phase – Phase test voltage: 100

 460V 50Hz 0.5Hz ; Phase – Neutral test voltage: 100  265V 50Hz 0.5Hz

Fault ring impedance (Phase – Earth)

Range (

)

Resolution (

) (*)

Accuracy

0.01

 9.99

0.01

(5%rdg + 3digits)

10.0

 199.9

0.1

200

 1999

1

(*) 0.1 m

 in range 0.0  199.9 m (with IMP57)

Maximum peak current at test voltage:

3.65A (127V) ; 6.64A (230V)

Phase – Earth test voltage 100

 265V 50Hz 0.5Hz

Global earth resistance (Ra ) without RCD tripping

Range (

) Resolution

(

)

Accuracy

1

 1999

1

 (5%rdg + 3digits)

Test current: 15mA ; Phase – Earth test voltage

: 100

 265V 50Hz 0.5Hz