6.1.2.1. Anomalous
situations
in "AUTO", "RT+", "RT-" mode
If the instrument detects
a voltage higher than
approx. 15V at the input
terminals, the message
to the side appears on
the display.
LOW
30.11.12
-.- -
R+ R-
-.--
-.--
---mA ---mA
VOLT IN INPUT
AUTO 0.11
The test cannot be
carried out because
voltage has been
detected at the
instrument’s inputs
FUNC
CAL
If the instrument detects
that:
R
CALIBRATION
> R
MEASURED
the message to the side
appears on the display.
LOW
30.11.12
0.00
R+ R-
0.00
0.00
219mA 219mA
CAL > RES
AUTO 0.11
CAUTION:
R
CALIBRATION
> R
MEASURED
FUNC
CAL
PREVIOUS RESULTS CANNOT BE SAVED.
In case a resistance
higher or equal to 5
but lower than 99,9
is
detected, at the end of
the test the instrument
gives out a long sound
and the following screen
appears on the display.
LOW
30.11.12
5.17
R+ R-
5.17
5.17
209mA 209mA
AUTO 0.11
Resistance higher than 5
Test current
FUNC
CAL
The results can be saved by pressing the SAVE key twice (see § 7.1).
In case a resistance
higher than 99,9
is
detected, at the end of
the test the instrument
gives out a long sound
and the following screen
appears on the display.
LOW
05.06.12
Resistance with a value
higher than 99.9
> 99.9
R+ R-
-.--
-.--
---mA ---mA
AUTO 0.11
CAUTION: Resistance
value out of range
FUNC
CAL
The results can be saved by pressing the SAVE key twice (see § 7.1).