Setting the Alarm Limits
Note: Low alarm limits are set by the two coarse and
fine potentiometers on the left. High alarm limits are set
by the two coarse and fine potentiometers on the right.
STEP 1.
Remove power from the instrument and disconnect the
signal input wires. Snap off the front panel lens. Apply power and
allow approximately 5 minutes of warm-up time.
STEP 2.
Set the HI/LO jumper (located between the display
digits and the adjustment potentiometers) from the normal position
to either the SET HI or the SET LO position. See drawing on page
15.
STEP 3.
Adjust the
coarse
potentiometer until the display reads
the value of the alarm limit. Make any final adjustments with the
fine adjust pot.
STEP 4.
Return the HI/LO jumper to its normal position.
STEP 5.
Install the front panel lens.
Ensure that power is
disconnected before reconnecting signal wires.