FIELD UPGRADE
Download Application
Contact PIE for upgrade files that can be loaded via PIE's STM32 Update Loader. This utility is
available on our website: www.pie-corp.com.
1. Power down the Omega JR and change the Boot Jumper (JP3) to LOAD. Refer to Diagram:
Top View of Omega JR Main Board to locate this jumper.
2. Power up the Omega JR.
3. Open STM32 Update Loader and use these settings:
Port Name:
Com port # for Diagnostics
Baud Rate:
256000
Parity:
Even
Echo:
Disabled
Timeout(s):
10
Select Next.
4. The screen will read: "Target is readable. Please click "Next" to proceed." If it does not have
this message (or a similar message), go back and verify that the jumper is set correctly and that
all of the settings on the previous page are correct. Also check that no other device is trying to
use the Diagnostics Com Port (HyperTerm, for example.)
Select Next.
5. Change Target to STM32_XL-density_768K
Select Next.
6. Make sure that “Download to device” is selected. Select the file in "Download from file".
Leave all other options on this page as they are.
Select Next.
7. Close STM32 Update Loader when complete.
8. Power down the Omega JR and change the Boot Jumper (JP3) back to RUN.