POWER WIRING INSTALLATION
Wiring Specifications (STRANDED COPPER WIRE)
On a Dual Gate System, each unit must be installed on ITS OWN separate circuits.
NOTE: Calculated using NEC guidelines. Local codes and conditions must be reviewed for suitability of wire installation. All power
wiring should be dedicated and protected. Location of primary power disconnect should be labeled.
To reduce the risk of SEVERE INJURY or DEATH:
• ANY maintenance to the operator or in the area near the
operator MUST NOT be performed until disconnecting the
electrical power and locking-out the power via the operator
power switch. Upon completion of maintenance the area
MUST be cleared and secured, at that time the unit may be
returned to service.
• Disconnect power at the fuse box BEFORE proceeding.
Operator MUST be properly grounded and connected in
accordance with local electrical codes. NOTE: The operator
should be on a separate fused line of adequate capacity.
• ALL electrical connections MUST be made by a qualified
individual.
• DO NOT install ANY wiring or attempt to run the operator
without consulting the wiring diagram. We recommend that
you install an optional reversing edge BEFORE proceeding with
the control station installation.
• ALL power wiring should be on a dedicated circuit and well
protected. The location of the power disconnect should be
visible and clearly labeled.
• ALL power and control wiring MUST be run in separate
conduit.
• BEFORE installing power wiring or control stations be sure to
follow ALL specifications and warnings described below.
Failure to do so may result in SEVERE INJURY to persons and/
or damage to operator.
ATTENTION
AVERTISSEMENT
AVERTISSEMENT
AVERTISSEMENT
WARNING
CAUTION
WARNING
WARNING
WARNING
PRECAUCIÓN
ADVERTENCIA
ADVERTENCIA
ADVERTENCIA
SINGLE PHASE
115 VAC
230 VAC
THREE PHASE
230 VAC
460 VAC
575 VAC
W I R I N G
WIRE GAUGE 6
• 1/2 HP Motor -------
425 ft. (129.5 m) 1845 ft. (562.4 m)
2557 ft. (779.4 m) 12789 ft. (3898.1 m) 15987 ft. (4872.8 m)
WIRE GAUGE 8
• 1/2 HP Motor -------
269 ft. (82 m)
1165 ft. (355.1 m)
1614 ft. (492 m)
8072 ft. (2460.4 m) 10089 ft. (3075.1 m)
WIRE GAUGE 10
• 1/2 HP Motor -------
168 ft. (51.2 m)
730 ft. (222.5 m)
1012 ft. (308.5 m) 5064 ft. (1543.5 m) 6330 ft. (1929.4 m)
WIRE GAUGE 12
• 1/2 HP Motor -------
105 ft. (32 m)
458 ft. (139.6 m)
634 ft. (193.2 m) 3171 ft. (966.5 m)
3964 ft. (1208.2 m)