Troubleshooting Diagram 17
NO
Did you make sure of
source 1 device of the RXD
instruction?
Are communication
parameters set correctly
using WindLDR?
Are inputs to more
than 5 RXD instructions
on simultaneously?
Data is not received correctly in the 
user communication mode.
Set the communication parameters to 
match those of the remote terminal 
using WindLDR. Web server CPU 
module can use constants only for start 
and stop delimiters. See “Programming 
WindLDR” of the basic volume (page 
10-5.)
Is the data register
designated as receive status
used repeatedly?
Correct the program to replace the 
duplicate data register with a different 
data register.
Is a start delimiter specified in
the RXD instruction?
Did you check the start
delimiter of incoming data?
Did you check the
format of incoming
data?
Is an end delimiter specified in
the RXD instruction?
Did you check the end
delimiter of incoming data?
Is the receive timeout
value set correctly using
WindLDR?
Is one input used to start
multiple RXD instructions?
Make sure that the receive format of 
the RXD instruction matches that of 
the incoming data.
Correct the program to make sure 
that inputs to more than 5 RXD 
instructions do not go on 
simultaneously.
Use one input to start one RXD 
instruction without a start delimiter.
Make sure that the start delimiter in 
the RXD instruction matches that of 
the incoming data.
Make sure that the end delimiter in 
the RXD instruction matches that of 
the incoming data.
Make sure that the receive timeout 
value is larger than character intervals 
of the incoming data.
Make sure that the receive data 
designated as the source 1 device is 
correct.
YES
YES
YES
YES
NO
NO
NO
NO
YES
YES
YES
NO
NO
NO
YES
NO
NO
YES
YES
NO
Call IDEC for assistance.