Gillette Generators SP-1500 User Manual
Page 13
![background image](/manuals/349917/13/background.png)
PAGE 13
WARNING: An open bottom, stationary gen-set must be installed over a non-combustible material, such as a
cement slab, and must be positioned to prevent combustible materials, rain, pooling water, sprinklers, etc. from
entering into, and accumulating under gen-set.
A) Installation should place gen-set as close as possible to the fuel supply, the transfer switch, and distribution/
circuit breaker panel.
B) Service access must be provided to allow generator housing doors to fully open.
C) Installation must prevent water, leaves, grass, snow, etc., from reaching top of generator skid base. Drainage
must be provided to keep concrete pad, free from standing water.
D) Always remove snow accumulation on roof when snow depth reaches 4”, or more.
E) Maximum ambient operating temperature is 105º F (40º C), for all gen-set sizes.
NOTE #1
NOTE #2
NOTE #3
NOTE #4
HEIGHT
NET WEIGHT
HEIGHT
NET WEIGHT
GEN-SET
MODEL
A B
C-1 C-2 D E F G H I I-1
IN.
CM.
LBS. KG IN. CM.
LBS. KG
SP-200 14 6 34 -
49
1/2 62 68 7 33 36 34 86 971 440 47 119 1371 622
SP-250 14 6 34 -
49
1/2 62 68 7 33 36 34 86 1070 485 47 119 1470 667
SP-300 14 6 34 -
49
1/2 62 68 7 36 36 34 86 1120 508 47 119 1520 689
SP-410
16 6
-
4 1/4
51 1/2 72
78
8 39 42 36
91 1326 601
53
134 1806 819
SP-520
16 6
-
4 1/4
51 1/2 72
78
8 39 42 38
97 1670 757
53
134 2150 973
SP-620
16 6
-
4 1/4
51 1/2 72
78
8 39 42 38
97 2097 951
53
134 2411 1094
SP-8005N 24 6
-
4 1/4 55 74 1/2 104
98 12 45 48 50 127 2097 943 72 1/2 183 2829 1283
SP-960
24 6
-
4 1/4 55 74 1/2 104
98 12 45 48 50 127 2229 1011 72 1/2 183 2979 1351
SP-1200 24 8
-
4 1/4 48 82 1/2 124 110 12 45 48 52 132 2424 1099 72 1/2 183 3174 1440
SP-1500 24 8
-
4 1/4 48 82 1/2 124 110 12 45 48 52 132 2684 1217 72 1/2 183 3594 1630
NOTE #1: HEIGHT FOR “OPEN” (NO ENCLOSURE) GEN-SET.
NOTE #2: NET WEIGHT FOR “OPEN” (NO ENCLOSURE) GEN-SET.
NOTE #3: HEIGHT FOR ENCLOSED GEN-SET.
NOTE #4: NET WEIGHT FOR ENCLOSED GEN-SET.
NOTE #5: ADD 18” TO HEIGHT FOR MUFFLER EXHAUST PIPE EXTENSION AND
ATTACHED RAIN CAP, ON WEATHER HOUSED SETS.
NOTE #6: WEIGHTS AND DIMENSIONS ARE APPROXIMATE AND MAXIMUM.
CONSULT FACTORY FOR EXACT FIGURES.
NOT
U
S
E
D
B
A
D
E
F
G
H
I
C-C
I-1
C-2
C-1
Battery Tray
Electrical Stub Up
(Exhaust Chute on
Enclosed Gen-Set)
(Air Intake Chute
on Enclosed
Super-Silent Gen
-Set)
External
Fuel Input
External
Fuel Input
FIGURE 4
Incoming Co
oling
Air