beautypg.com

Mks series, General pump – General Pump MKS Owner Manual User Manual

Page 11

background image

GENERAL PUMP

A member of the Interpump Group

MKS SERIES

Page 11

9.4 Hydraulic Connections

In order to isolate the system from the vibrations produced

by the pump, we advise to build the first section of the duct

near the pump (both for intake and delivery) with flexible

hose. The consistency of the intake section must allow to

avoid deformation caused by the depressurization

produced by the pump.

9.5 Pump Feeding

MKS pumps must always be installed under positive

head, i.e. they must receive water by gravity or by forced

feeding, and never suck from a lower level. The pumps

can tolerate minimum NPSH even as low as 1 m. (3.28

ft.), however, to obtain a better volumetric efficiency and

above all to avoid cavitation, the minimum NPSH avail-

able, measured at the pump inlet flange, will have to be at

least equal or higher than the values shown in the chart

below.

9.6 Suction Line

For the pump’s correct operation, the suction line must

have the following characteristics:

1. Minimum internal diameter as indicated in the diagram

in paragraph 9.9, and in any case equal or greater than

the pump head’s value.

Along the duct, avoid localized diameter reductions

that may cause pressure drops with subsequent

cavitation. Absolutely avoid 90

0

elbows, connections with

other hoses, bottlenecks, counter-slopes, upside down “U”

shaped curves, “T” connections.

2. The selected lay-out must allow to avoid cavitation.

3. It should be perfectly airtight, and built in a way that

guarantees perfect sealing over time.

4. Avoid pump emptying when stopping (even partial

emptying).

5. Do not use hydraulic-type fittings, 3 or 4 way fittings,

adapters, etc. , since they may hinder the pump’s

performance.

6. Do not install Venturi tubes or injectors for detergent

intake.

7. Avoid the use of standing valves, check valves, or any

other type of one-way valves.

8. Do not connect the by-pass line from the valve directly

to the pump suction line.

9. Provide appropriate baffle plates inside the tank in

order to avoid water flows coming from both the by-

pass and feeding lines may create turbulance near the

tank’s outlet port.

10. Make sure that the suction line is perfectly clean inside

before connecting it to the pump.

11. The pressure gauge for checking booster pressure

must be installed near the plunger pump’s outlet port,

and always after the filters.

The version may be changed only by special-

ized and authorized personnel by carefully

following the instructions in the repair manual.

9.3 Version Change and Reducer Positioning

A right version pump is defined when: observing the

pump from the head side, the PTO shank of the pump

shaft is on the right side.

A left version pump is defined when: observing the pump

from the head side, the PTO shank is on the left side.

See fig. 5.

Furthermore, it is possible to position the reducer in 5

different positions, both on the right and left sides, as

shown in fig. 6.

The reducer’s position may be changed only

by specialized and authorized personnel by

carefully following the instructions in the

repair manual.

fig. 6

MKS40A MKS45A MKS50A MKS55A MKS60A MKS65A

NPSH

r

(ft)

14.8

18

21.3

24.6

26.2

29.5

For the pumps with higher displacement (MKS55A-60A-

65A), it is strongly recommended to use a booster pump

to avoid cavitation, in view of the geometry on the

hydraulic section and of the remarkably high flow rates.

The booster pump must have the following specifications:

flow rate at least double the rated flow rate of the pump,

and pressure between 30 to 45 PSI (2 to 3 Bar). These

feeding conditions must be respected in all running condi-

tions.

Booster start-up must always precede plunger

pump start-up. In order to protect the pump,

we advise to install a pressure switch on the

feeding line after the filters.

Ref 300670 Rev. B

05-13