Hydronic piping – Lochinvar 000 - 500 User Manual

Page 24

background image

24

4

Hydronic piping

Installation & Service Manual

RELIEF VALVE

Figure 4-1_Relief Valve - CBN315-500

This appliance is supplied with a relief valve(s) sized in
accordance with ASME Boiler and Pressure Ves

sel Code,

Section IV (“Heating Boilers”). The re lief valve(s) is mounted
directly into the heat ex

chang

er inside the header (see

FIG.’s 4-1 and 4-2). To pre vent water damage, the dis charge
from the relief valve shall be piped to a suit able floor drain for
disposal when relief occurs. No reducing couplings or other
restrictions shall be installed in the discharge line. The
discharge line shall allow complete drainage of the valve and
line. Relief valves should be manually operated at least once a
year.

ƽ CAUTION

Avoid contact with hot discharge water.

FLOW SWITCH

Figure 4-2_Water Flow Switch - CBN315-500

A water flow switch is available as a factory sup plied option on
all heating boilers and water heaters (see section 7). The flow
switch should be wired between terminals X and B. Remove the
jumper between the X and B terminals on the terminal strip.
This wiring connection installs the flow switch in the 24 VAC
safety cir cuit to prove water flow before main burner ig ni tion. A
flow switch installed with the fac

to

ry sup

plied minimum

adjustment setting requires a spe cif ic minimum flow to make
the switch and start burner operation. The flow rate required is
a function of the diameter of pipe and tee used for installation.
Ensure that the pump installed on the boiler will supply
adequate flow to make the flow switch con tacts and operate the
appliance.

Relief Valve

Water Flow Switch (if equipped)

This manual is related to the following products: