Reconnection/Adjustments 27
200--240-Volt Configurations
The 200--240-volt configuration does not use a jumper
lead.
If the unit was originally wired for straight
100--120 volt, 3 wire, remove the jumper lead (see
Figure 8-1 for location).
4
3
2
1
Stator Leads
L0
GRD.
L1
L0 (Neutral)
Line
Side
Single-Pole
Circuit
Breaker
Ground
Load
Side
200--220--240 Volt
2 Wire
Tape to insulate
from ground
60 Hz
L0--L1
200-240 Volt
Figure 8-4
200--220--240-Volt, 2-Wire Configuration
for Models with ADC 2100