5.8

Flash adaptation

The function is only active in automatic mode (

).

Direct reactions to deviations in room temperature can be achieved using the function block set-
ting: FB2 = ON. A gradient characteristic (FB19 = OFF) must be configured.
Flash adaptation counteracts room temperature deviations by increasing or decreasing the
level of the heating characteristic by up to 5 °C. The corrections are made after 10 minutes by
1 °C. The corrected value is indicated in the parameter level under the datapoint for

Level, flow.

Note!
Cooling loads, such as drafts or open windows, affect the control process!
Rooms may be temporarily overheated when the cooling load has been eliminated!

Functions

WE

Configuration

Flash adaptation

OFF

FB2 = ON

Characteristic

OFF

FB19 = OFF

Parameter

WE

Range of values

Room set point

20 °C

0 to 40 °C

5.9

Adaptation

The function is only active in automatic mode (

).

The controller is capable of automatically adapting the heating characteristic to the building
characteristics, provided a gradient characteristic has been set (FB19 = OFF). The reference
room, where the room sensor is located, represents the entire building and is monitored to en-
sure that the

Room set point is maintained. When the mean measured room temperature in

rated operation deviates from the adjusted set point, the heating characteristic is modified ac-
cordingly for the following time-of-use. The corrected value is displayed in the parameter level
under

Gradient, flow.

Function

WE

Configuration

Adaptation

OFF

FB1 = ON

Characteristics

OFF

FB19 = OFF

Parameter

WE

Range of values

Room set point

20 °C

0 to 40 °C

EB 5476 EN

47

Functions of the heating circuit