5.8
Flash adaptation
The function is only active in automatic mode (
).
Direct reactions to deviations in room temperature can be achieved using the function block set-
ting: FB2 = ON. A gradient characteristic (FB19 = OFF) must be configured.
Flash adaptation counteracts room temperature deviations by increasing or decreasing the
level of the heating characteristic by up to 5 °C. The corrections are made after 10 minutes by
1 °C. The corrected value is indicated in the parameter level under the datapoint for
Level, flow.
Note!
Cooling loads, such as drafts or open windows, affect the control process!
Rooms may be temporarily overheated when the cooling load has been eliminated!
Functions
WE
Configuration
Flash adaptation
OFF
FB2 = ON
Characteristic
OFF
FB19 = OFF
Parameter
WE
Range of values
Room set point
20 °C
0 to 40 °C
5.9
Adaptation
The function is only active in automatic mode (
).
The controller is capable of automatically adapting the heating characteristic to the building
characteristics, provided a gradient characteristic has been set (FB19 = OFF). The reference
room, where the room sensor is located, represents the entire building and is monitored to en-
sure that the
Room set point is maintained. When the mean measured room temperature in
rated operation deviates from the adjusted set point, the heating characteristic is modified ac-
cordingly for the following time-of-use. The corrected value is displayed in the parameter level
under
Gradient, flow.
Function
WE
Configuration
Adaptation
OFF
FB1 = ON
Characteristics
OFF
FB19 = OFF
Parameter
WE
Range of values
Room set point
20 °C
0 to 40 °C
EB 5476 EN
47
Functions of the heating circuit