6 set ting the times-of-use 12, Set ting 12, Setting the times-of-use – Samson 5476 User Manual
Page 12: 6 setting the times-of-use
1.6
Setting the times-of-use
Two times-of-use can be set for each day of the week. If only one time-of-use is required, the
start and stop times of the second time-of-use must be programmed to identical times.
The times schedules are set for the required control circuits one after the other in the parameter
level.
Time schedule
Display
Heating circuit 1
Heating circuit 2 (Anl 9: underfloor heating circuit)
(second set of parameters after datapoint for vacation mode)
DHW circuit
Circulation pump
Parameters of the heating circuit
WE
Range of values
Period/day
1–7
1–7, 1–5, 5–6, 1, 2, 3, 4, 5, 6, 7 with
1–7 = daily, 1–5 = Monday to Friday
6–7 = Saturday to Sunday
1 = Monday, 2 = Tuesday, …, 7 = Sunday
Start first time-of-use
7:00
00:00 to 24:00h; in steps of 30 minutes
Stop first time-of-use
12:00
00:00 to 24:00h; in steps of 30 minutes
Start second time-of-use
12:00
00:00 to 24:00h; in steps of 30 minutes
Stop second time-of-use
22:00
00:00 to 24:00h; in steps of 30 minutes
Proceed as follows:
Switch to the parameter level.
Display: Time,
blinks
12
EB 5476 EN
Operation
0 1 2
3 4
5
6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24