7 three-step con trol 61, Con den sa te ac cu mu la ti on con trol 61, Time de lays, com pen sa ting for 61 – Samson Trovis 5100 User Manual
Page 61: Three-step control, 5 condensate accumulation control, 6 compensating for time delays
7.5 Condensate accumulation control
Activate the Condensate accumulation control function to start up condensate accumulation
plants, in particular to avoid problematic excess temperatures. The controller response to set
point deviations which cause the primary valve to open is attenuated. The controller response to
set point deviations which cause the control valve to close remains unaffected.
In systems Anl 6 and 9, the limitation applies to all control valves; in all other systems, it applies
to the control valve with the highest flow temperature set point.
In systems with DHW heating on the primary side (Anl 7 and 8), the Condensate accumulation
control
function must configured separately under Co4.
Functions
WE
Configuration
Condensate accumulation control
OFF
2 °C
Co5 -> Fb07 = ON
Maximum system deviation / 2 to 10 °C
Condensate accumulation control
(Anl 7 and 8)
2 °C
Co4 -> Fb13 = ON
Maximum system deviation / 2 to 10 °C
Note!
The condensate accumulation control function can only be activated when no on/off control has
been configured, i.e. Co5 -> Fb14 = ON.
7.6 Compensating for time delays
The controller regulates the control circuit with the highest flow set point with the secondary flow
sensor. If the sensor is placed on the secondary side directly downstream of the heat exchanger
and the setting Co5 -> Fb06 = ON configured, any time delays due to changes in temperature
at a distant flow sensor do not occur anymore. This measure used with a condensate accumula-
tion control means that the control can intervene before the control valve releases
unproportionally too much heat exchanger area.
Functions
WE
Configuration
Flow sensor, secondary VFsek
ON
Co5 -> Fb00 = ON
Compensation of time delays
OFF
Co5 -> Fb06 = ON
EB 5179 EN
61
System-wide functions