IRIS MODEL P522 APPLICATION MANUAL

Page 32

Registers Map

4X OR NUMERICAL REGISTERS:

400001

Flame Count Of Active Channel (read only)

400002

Processor Status (read only)

400002/0 View head/Channel Selected (0=Channel A)
400002/1 Flame On Relay Status
400002/2 Processor Lockout Status (0=lockout)
400002/3 Panel Access Disabled (0=disabled)
400002/4 4-20 output Status (0=0-40)
400003

Flame On Channel A

400004

Flame On Channel B

400005

Flame Off Channel A

400006

Flame Off Channel B

400007

Gain Channel A

400008

Gain Channel B

400009

IR Analog Gain Channel A

400010

IR Digital Gain Channel A

400011

IR Filter Channel A

400012

UV Gain Channel A

400013

IR Analog Gain Channel B

400014

IR Digital Gain Channel B

400015

IR Filter Channel B

400016

UV Gain Channel B

400017

View Head Type Channel A (read only)

400018

View Head Type Channel B (read only)

400019

Temperature Channel A (read only)

400020

Temperature Channel B (read only)

400021

Time Delay on (Upper nibble = B lower = A)

400022

FFRT (Upper nibble = B lower = A)

400023

Firmware Version # (read only)

0X OR DISCRETE REGISTERS:

(All read only)

000001

View head/Channel Selected (0=Channel A)

000002

Flame On Relay Status

000003

Processor Lockout Status (0=lockout)

000004

Panel Access Disabled (0=disabled)

000005

4-20 output Status (0=0-40)

Communicating with Modicon PLC

Each Modicon PLC comes with a Modbus port. The
control program can read/write the settings from/to
the P520/P522 scanner via this port. A XMIT
loadable module is needed to send Modicon func-
tions. XMIT loadable module is available from
Modicon Inc.

Note: Not all models of Modicon PLC’s
will accept the XMIT loadable module.
Please consult you local Modicon dealer
for more information.

Communication with Human-Interface
Host Computer

A number of Modbus drivers for Microsoft Window
95 and NT are available from the third party devel-
oper, such as Rockwell Software’s WinTelligent
Linx Modicon. A Modicon driver allows applica-
tion programs such as Microsoft Excel, Wonderware
and RSView to communicate with the P520/P522
scanners directly.

RS-232 to RS-422 CONVERSION

It is necessary to use a RS-232 to RS-422 converter
at the host computer. The IRIS COMM converter
module can be used, and is recommended because
of its photocoupler isolation. The converter must
have galvanic ground isolation.

SETTING ADDRESSES

Each P522 must have its own unique address. The
address is easy to change. Press the RESET push-
button for >2 seconds, causing the P522 to immedi-
ately display its address on the four-digit display
(0000 to 0063), and change using the UP or DOWN
arrow buttons. When the desired address is dis-
played, push the STORE button, and the P522 will
immediately respond to this new address.

In current software revisions of the processor (ver-
sions 3.0 and higher), the baud rate can also be changed
when the module address is changed. The baud rate
is displayed in the highest two digits of the numeric
display (i.e., 4802 is 4800 baud and address 2). To
change to 9600 baud, increase the display past 4863.
The next display will be 9600, which is 9600 baud,
address 0. Then increase the display further to the
desired address. To return to 4800 baud, reduce the
display below 9600, and set the desired address.