Communicating with modicon plc, Communication with human-interface host computer, Setting addresses – I.R.I.S. FLAME MONITORING SYSTEM P522 User Manual
Page 32

IRIS MODEL P522 APPLICATION MANUAL
Page 32
Registers Map
4X OR NUMERICAL REGISTERS:
400001
Flame Count Of Active Channel (read only)
400002
Processor Status (read only)
400002/0 View head/Channel Selected (0=Channel A)
400002/1 Flame On Relay Status
400002/2 Processor Lockout Status (0=lockout)
400002/3 Panel Access Disabled (0=disabled)
400002/4 4-20 output Status (0=0-40)
400003
Flame On Channel A
400004
Flame On Channel B
400005
Flame Off Channel A
400006
Flame Off Channel B
400007
Gain Channel A
400008
Gain Channel B
400009
IR Analog Gain Channel A
400010
IR Digital Gain Channel A
400011
IR Filter Channel A
400012
UV Gain Channel A
400013
IR Analog Gain Channel B
400014
IR Digital Gain Channel B
400015
IR Filter Channel B
400016
UV Gain Channel B
400017
View Head Type Channel A (read only)
400018
View Head Type Channel B (read only)
400019
Temperature Channel A (read only)
400020
Temperature Channel B (read only)
400021
Time Delay on (Upper nibble = B lower = A)
400022
FFRT (Upper nibble = B lower = A)
400023
Firmware Version # (read only)
0X OR DISCRETE REGISTERS:
(All read only)
000001
View head/Channel Selected (0=Channel A)
000002
Flame On Relay Status
000003
Processor Lockout Status (0=lockout)
000004
Panel Access Disabled (0=disabled)
000005
4-20 output Status (0=0-40)
Communicating with Modicon PLC
Each Modicon PLC comes with a Modbus port. The
control program can read/write the settings from/to
the P520/P522 scanner via this port. A XMIT
loadable module is needed to send Modicon func-
tions. XMIT loadable module is available from
Modicon Inc.
Note: Not all models of Modicon PLC’s
will accept the XMIT loadable module.
Please consult you local Modicon dealer
for more information.
Communication with Human-Interface
Host Computer
A number of Modbus drivers for Microsoft Window
95 and NT are available from the third party devel-
oper, such as Rockwell Software’s WinTelligent
Linx Modicon. A Modicon driver allows applica-
tion programs such as Microsoft Excel, Wonderware
and RSView to communicate with the P520/P522
scanners directly.
RS-232 to RS-422 CONVERSION
It is necessary to use a RS-232 to RS-422 converter
at the host computer. The IRIS COMM converter
module can be used, and is recommended because
of its photocoupler isolation. The converter must
have galvanic ground isolation.
SETTING ADDRESSES
Each P522 must have its own unique address. The
address is easy to change. Press the RESET push-
button for >2 seconds, causing the P522 to immedi-
ately display its address on the four-digit display
(0000 to 0063), and change using the UP or DOWN
arrow buttons. When the desired address is dis-
played, push the STORE button, and the P522 will
immediately respond to this new address.
In current software revisions of the processor (ver-
sions 3.0 and higher), the baud rate can also be changed
when the module address is changed. The baud rate
is displayed in the highest two digits of the numeric
display (i.e., 4802 is 4800 baud and address 2). To
change to 9600 baud, increase the display past 4863.
The next display will be 9600, which is 9600 baud,
address 0. Then increase the display further to the
desired address. To return to 4800 baud, reduce the
display below 9600, and set the desired address.