beautypg.com

Troubleshooting tips, Before you call for service – GE 5500 User Manual

Page 19

background image

Safety Instructions

Operating Instructions

Care and Cleaning

Troubleshooting T

ips

Customer Service

Before You Call For Service…

www.GEAppliances.com

Troubleshooting Tips

Problem

Possible Causes

What To Do

Zoneline does

The unit is

• Make sure the Zoneline plug is pushed completely

not start

unplugged.

into the outlet.

The fuse is blown/circuit

• Check the house fuse/circuit breaker box and replace

breaker is tripped.

the fuse or reset the breaker.

The unit is waiting for

• This is normal. The Zoneline will start again after

the compressor overload

it resets.

protector to reset.

Power failure.

• If power failure occurs, set the mode control to STOP.

When power is restored, set the mode control to the
desired setting.

• There is a protective time delay (up to 3 minutes) to

prevent tripping of the compressor overload. For this
reason, the unit may not start normal heating or cooling
for 3 minutes after it is turned back on.

Zoneline does not cool

Indoor airflow

• Make sure there are no curtains, blinds or furniture

or heat as it should

is restricted.

blocking the front of the Zoneline.

Outdoor airflow is

• Make sure the rear grille is not restricted. This can cause

restricted or recirculated.

the unit to cycle off due to the compressor overload.

• Outdoor grille must have a minimum of 65% free area.

Non-GE grilles may be too restrictive for proper
performance. Consult your salesperson for assistance.

The temp control may

• Turn the control to a lower or higher setting.

not be set high enough.

NOTE: The temperature limiter may be limiting the temperature range.

The air filter is dirty.

• Clean the filter at least every 30 days.

See the Operating Instructions section.

The room may have

• When the Zoneline is first turned on you need to

been hot or cold.

allow time for the room to cool down or warm up.

Outdoor air is

• Set the vent control to the CLOSE position.

entering the room.

Burning odor at the start

Dust is on the surface

• This can cause a “burning” odor at the beginning of

of heating operation

of the heating element.

the heating operation. This odor should quickly fade.

The air is not always

The heat pump is not

• This is normal. The heat pump will produce warm air

cool or hot during

producing hot air.

but not as hot as air produced when the higher-cost

operation

electric heat is used.

The fan switch may be

• This causes the fan to blow room temperature air

set at continuous fan

even when the compressor or heater cycles off.
The continuous air movement provides better
overall temperature control.

The air does not feel

The heat pump alone

• Use the Electric Heat Option. This turns off the

warm enough during

produces air that feels

heat pump and warms with electric heat only.

heating operation

cooler than desired.

NOTE: Use of this option will result in increased energy
consumption.

Temperature display

The compressor may

• Set the mode control to STOP and then restart the

flashes

have failed.

unit. If the flashing light reappears within 30 minutes,
call for service.

19