Installation instructions, 265 volt electrical supply, Reinstall junction box – GE 5500 User Manual
Page 16: Reinstall junction box cover, Power connection chart
Installation Instructions
16
265 VOLT ELECTRICAL SUPPLY
REINSTALL JUNCTION BOX
• Reinstall the junction box by engaging the tab at the
lower rear, aligning the screw hole at the top and
driving the one screw until secure. Be sure that all
wire leads are inside the box and not pinched
between the box and the unit. The green insulated
ground wire from the unit MUST be connected to
the branch circuit ground wire.
Make all wire connections by using appropriate
UL-listed electrical connectors and techniques
(black to black, white to white and green to green).
4
REINSTALL JUNCTION
BOX COVER
1 Carefully tuck all wires and
connections back inside the
junction box. Be sure there
are no loose connections or
stray uninsulated wires
exposed.
2 Place the junction box cover
in place. Replace the two
screws removed earlier and
tighten securely.
3 Discard the unused portion of the plug and
the cordset.
5
230/208 Volt
Power
Wall Plug
Heater Wattage
Supply Kits
Configuration
Circuit Protective Device
@ 230/208 Volts
RAK3152
Tandem
15 Amp Time Delay Fuse or Breaker
2.55/2.09 KW
RAK3202
Perpendicular
20 Amp Time Delay Fuse or Breaker
3.45/2.82 KW
RAK3302*
Large Tandem
30 Amp Time Delay Fuse or Breaker
5.00/4.10 KW
265 Volt
Power
Wall Plug
Heater Wattage
Supply Kits
Configuration
Circuit Protective Device
@ 265 Volts
RAK5152
Does Not Apply
15 Amp Time Delay Fuse or Breaker
1.7 KW
RAK5172
Does Not Apply
15 Amp Time Delay Fuse or Breaker
3.0 KW
RAK5202
Does Not Apply
20 Amp Time Delay Fuse or Breaker
3.7 KW
RAK5302*
Does Not Apply
30 Amp Time Delay Fuse or Breaker
5.0 KW
* Not recommended for use on 7000 BTUH units.
POWER CONNECTION CHART