beautypg.com

Troubleshooting – GSI Outdoors 100 SERIES DRYER PNEG-552 User Manual

Page 60

background image

60

PNEG-552 100 Series Dryer

10. Troubleshooting

Burner operates but does not cycle from high-fire to
low-fire.

1. Check the gas pressure reading on the gauge. Problem may be

due to insufficient gas regulator setting. Temporarily decrease
the High-Low Fire thermostat setting to verify that the
thermostat will function and cause the burner to cycle. If burner
will cycle at the reduced thermostat setting, it indicates that the
problem was due to insufficient heat to satisfy the original
setting. Increase the gas regulator setting for additional
heat output. Do not exceed the maximum pressure listed in
this manual.

2. High-Low Fire thermostat control may be defective. If the burner

still does not cycle to low-fire after decreasing the thermostat,
the problem may be due to a broken or kinked thermostat
sensor tube. Observe reading on the thermometer. Replace
control assembly if it cannot be set to cause its switch to go
to the open circuit position with normally hot air plenum
temperatures.

3. If the burner continues to operate on high-fire, check the

high-fire gas solenoid valve for a stuck or blocked open
condition, or for reversed gas pipe connections. The solenoid
valve must not allow gas flow when its coil is not energized.

Burner operates but does not cycle from low-fire
to high-fire.

1. Check for an excessive low-fire gas pressure setting. Observe

pressure setting shown on gauge, and compare reading with
recommended low pressure settings listed in this manual.
Readjust low-fire setting on flow control valve, if necessary.

2. Check for improperly adjusted or defective High-Low Fire

thermostat control. Temporarily increase the temperature
setting. If the heater will still not cycle, check for problem in the
control wire connections. The control wires should be connected
to terminals R and B of the thermostat, so the switch will open
upon temperature rise. If the burner will cycle with these two
wires connected together, the thermostat is faulty.

3. Check for improperly connected or faulty high-fire gas vapor

solenoid valve. Correct any poor connections or defective
wiring. If wiring appears proper, problem may be caused by a
burned out valve coil or defective valve. Replace high-fire
solenoid valve, or its coil, if defective.

If the Load and Unload Auger does not start but
everything else seems to work.

Check the fuse on the I/O Board in the back of the lower
control Box.

Problem

Possible Cause