5. Electric wiring

WARNING

DANGER OF BODILY INJURY OR DEATH

TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE
MAKING ANY ELECTRIC CONNECTIONS. GROUND CONNECTIONS MUST BE
COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS.

(1) Selection of size of power supply and interconnecting wires.

Precautions for Electric wiring

Electric wiring work should be conducted only by authorized personnel.
Do not connect more than three wires to the terminal block. Always use round type crimped terminal
lugs with insulated grip on the ends of the wires.
Use copper conductor only.

Select wire sizes and circuit protection from table below. (This table shows 20 m length wires with
less than 2% voltage drop.)

(2) Wiring connection

Make wiring to supply power to the indoor unit, so that the power for the outdoor unit is supplied by
terminals.

Item

Model

Phase Switch breaker

(A)

Circuit breaker

Overcurrent protector

rated capacity (A)

Power source

wire size

(minimum)

(mm

2

)

30

20

2.5

Switch

breaker(A)

Earth leakage breaker

Leak

current(mA)

30

Installation Manual For Indoor Unit

30

1

40

26

2.5

40

For series 242 282

3

L N

1 2 3

Y/G

INDOOR UNIT
TERMINAL BLOCK

POWER

1PH, 220-230V~, 50Hz

SUPPLY:

Y/G

1 2 3

OUTDOOR UNIT

TERMINAL BLOCK

For series 182

1

40

26

6.0

40

For series 282

For series
282 362 422 482

30

20

4.0

30

3

For series522

30

30

30

30

1

40

26

4.0

40

For series 242

1 2 3 N L

1 2 3

POWER

1PH, 220-230V~, 50Hz

SUPPLY:

For series 182

For series 282 362 422 482 522

OUTDOOR UNIT
TERMINAL BLOCK

INDOOR UNIT
TERMINAL BLOCK

POWER SUPPLY: 380-400V, 3N~, 50Hz

R S T N 1 2 3

1 2 3

Y/G

Y/G

Make wiring to supply power to the outdoor unit, so that the power for the indoor unit is supplied by
terminals.

INDOOR UNIT
TERMINAL BLOCK

OUTDOOR UNIT

TERMINAL BLOCK