When Trouble Happens

Error display ( For EAA series )

For remote

type, flash

times

1

2

3

4

5

6

7

8

9

10

1

1

12

13

15

17

18

19

20

Failure description

Indoor ambient temp. sensor failure

Indoor coil temp. sensor failure

Outdoor ambient temp. sensor failure

Outdoor coil temp. sensor failure/Compressor

dischar

ging temp. sensor abnormal

Over

-current protection

High/Low pressure abnormal

Power supply abnormal

Communication between wired

controller and indoor abnormal

Communication between indoor and outdoor abnormal

Drainage system abnormal

Outside alarm signal input

Gas pipe temp. sensor abnormal

T

emperature protection malfunction

EEPROM abnormal

Compressor overheat

Abnormal mode

Outdoor coil B(suction temp sensor

-for MR

V

II)

Outdoor dischar

ging B(oil temp sensor

-for MR

V

II)

Reason

Sensor broken down or short circuit for more than 2m continuously

Sensor broken down or short circuit for more than 2m continuously

Sensor broken down or short circuit for more than 2m continuously

Sensor broken down or short circuit for more than 2m continuously

CT

check abnormal 3 times in 30m

High pressure switch acts 3 times in 30m/Low pressure switch acts

in normal running

Fault phase, short of phase, out of balance greatly

Communication abnormal for more than 4m continuously

Communication abnormal for more than 4m continuously

Float switch broken down for more than 25m continuously

Outside signal broken down for more than 10s

Sensor broken down or short circuit for more than 2m continuously

Solenoid valve act incorrectly 3 times continuously

EEPROM data missing

The dischar

ging temperature is higher than 120degree

Indoor operation mode is dif

ferent with the running indoor unit.

Sensor broken down or short circuit for more than 2m continuously

Sensor broken down or short circuit for more than 2m continuously

Remarks

Failure code

on wired

controller

01(01H)

02(02H)

74(4AH)

73(49H)

72(48H)

83(53H)

71(47H)

07(07H)

06(06H)

08(08H)

1

1(0BH)

03(03H)

13(0DH)

05(05H)

80(50H)

12(0CH)

75(4BH)

77(4DH)

For central

control,

failure code

01D

02D

1

1D

12D

10D

14D

22D

06D

06D

21D

30D

20D

31D

17D

15D

23D

18D

15D

shows resumable fault, * shows it is not resumable fault.

Resumable if lower than 100 degree