MAIN FUNCTIONS
HOW TO SEE THE SETPOINT

1. Push and immediately release the SET key:

the display will show the Set point value.

HOW TO CHANGE THE SETPOINT

1. Push the SET key for more than 2 seconds to change the

Set point value;

2. The value of the set point will be displayed and the LED

starts blinking;

3. To change the Set value push the UP or DOWN arrows

within 10s.

4. To memorise the new set point value push the SET key

again or wait 10s.

HOW TO START A MANUAL DEFROST

Push the DEF key for more than 2 seconds

and a manual defrost will start.

HOW TO CHANGE A PARAMETER VALUE

To change the parameter’s value operate as follows:

1. Use “UP” or “DOWN” to change its value.

2. Press “SET” to store the new value and move to the

following parameter.

To exit: Press SET + UP or wait 15s without pressing a key.

NOTE: the set value is stored even when the procedure is

exited by waiting the time-out to expire.
THE HIDDEN MENU

The hidden menu Includes all the parameters of the instrument.

HOW TO ENTER THE HIDDEN MENU

1. Enter the Programming mode by

pressing the Set + DOWN key for 3s

(LED 1 and start blinking).

2. When a parameter is displayed keep

pressed the Set + DOWN for more than 7s.

The Pr2 label will be displayed immediately

followed from the HY parameter.

Label Characteristic

Description

Menu/User

Level

Possible

Settings

DEFAULT SETTINGS

Low

Temp.

Medium

Temp.

High

Temp.

REGULATION

SEt

Set Point

LS ~ US

-10

34

38

Hy

Differential

(0,1 ÷ 25,5°C / 1÷255 °F) Intervention

differential for set point. Compressor

Cut IN is Set Point + differential (Hy).

Compressor Cut OUT is when the

temperature reaches the set point

Pr1

1~ 45

3

3

3

LS

Minimum set point (- 50°C÷SET/-58°F÷SET): Sets the minimum

value for the set point..

Pr2

-67 ~ SET

-23

25

33

US

Maximum set point (SET÷110°C/ SET÷230°F). Set the maximum

value for set point.

Pr2

SET ~ 302F

37

40

45

Ot

Thermostat probe

calibration

(-12.0÷12.0°C; -120÷120°F) allows to adjust

possible offset of the thermostat probe

Pr2

-21~21

0

0

0

OdS Outputs activation

delay at start up

(0÷255min) This function is enabled at

the initial start up of the instrument and

inhibits any output activation for the period

of time set in the parameter

Pr2

0 ~ 255

minutes

0

0

0

AC

Anti-short cycle

delay

(0÷50 min) minimum interval between the

compressor stop and the following restart

Pr2

0 ~ 50

minutes

4

4

4

COF

Compressor OFF

time with faulty

probe

(0÷255 min) time during which the

compressor is OFF in case of faulty

thermostat probe. With COF=0

compressor is always active

Pr2

0 ~ 255

minutes

6

6

6

NOW YOU ARE IN THE HIDDEN MENU.

3. Select the required parameter.

4. Press the “SET” key to display its value (Now only the LED

is blinking).

5. Use UP or DOWN to change its value.

6. Press “SET” to store the new value and move to the

following parameter.

To exit: Press SET + UP or wait 15s without pressing a key.

NOTE: the set value is stored even when the procedure is

exited by waiting the time-out to expire.

HOW TO SEE THE ALARM DURATION AND MAX (MIN)

TEMPERATURE

If the alarm LED is on, an alarm has taken place.

To see the kind of alarm, the max (min) reached temperature

and alarm duration do as follows:v

1. Push the Up or Down key.

2. On the display the following message is shown::

HAL” for high temperature alarm (“LAL” for the

minimum allarm), followed by the Maximum

(minimum) temperature.

Then the “tiM” (tiMe) message is displayed, followed by

the “Duration” in h.mm.

3. Then the instrument displays the temperature once

again.

NOTE1: if an alarm is still occurring the “tim” shows the

partial duration.

NOTE2: the alarm is recorded when the temperature come

back to normal values
HOW TO RESET A RECORDED ALARM OR ONE THAT IS

STILL OCCURRING

1. Hold the SET key pressed for more than 3s, while the

recorded alarm is displayed. (the rSt message will be

displayed)

2. To confirm the operation, the “rSt” message starts

blinking and the normal temperature will be displayed

DEFAULT PARAMETER SETTINGS