DISPLAY

CF

Temperature

measurement unit

°C=Celsius; °F=Fahrenheit. WARNING: When

the measurement unit is changed the SET

point and the values of the parameters Hy,

LS, US, Ot, ALU and ALL have to be checked

and modified if necessary

Pr2

°C = Celsius

°F

=Fahrenheit

°F

°F

°F

DEFROST

tdF

Defrost type

EL = electrical heater; in = hot gas

Pr2

EL = electric

defrost / in

= hot gas

defrost

EL

EL

EL

dtE

Defrost termination

temperature

(-50÷50 °C/ -58÷122°F) (Enabled only when

EdF=Pb) sets the temperature measured by

the evaporator probe, which causes the end

of defrost

Pr1

-58~122

65

65

38

IdF

Interval between

defrost cycles

(0÷120h) Determines the time interval

between the beginning of two defrost cycles

Pr1

0 ~ 120

hours

6

6

6

MdF (Maximum) length

for defrost

(0÷255min) When P2P = n, (not evaporator

probe: timed defrost) it sets the defrost

duration, when P2P = y (defrost end based

on temperature) it sets the maximum

length for defrost

Pr2

0 ~ 255

minutes

40

40

60

Fdt

Drip time

(0÷120 min) time interval between reaching

defrost termination temperature and the

restoring of the control’s normal operation.

This time allows the evaporator to eliminate

water drops that might have formed due

to defrost

Pr1

0 ~ 255

minutes

2

2

0

FANS (XR60CX ONLY)

Fnd Fans delay after

defrost

(0÷255min) Interval between end of defrost

and evaporator fans start

Pr1

0 ~ 255

minutes

2

2

Not

Applicable

Fct

Temperature

differential

avoiding short

cycles of fans

(0÷59°C; Fct=0 function disabled). If the

difference of temperature between the

evaporator and the room probes is more

than the value of the Fct parameter, the

fans are switched on

Pr2

0~90

10

10

Not

Applicable

FSt

Fans stop

temperature

(-50÷50°C/122°F) setting of temperature,

detected by evaporator probe, above

which fans are always OFF

Pr1

-58~122

35

35

Not

Applicable

ALARMS

ALC Temperature alarms

configuration

(Ab; rE) Ab= absolute temperature: alarm

temperature is given by the ALL or ALU

values. rE = temperature alarms are

referred to the set point. Temperature alarm

is enabled when the temperature exceeds

the “SET+ALU” or “SET-ALL” values

Pr2

rE = relative

to set point

Ab =

absolute

Ab

Ab

Ab

ALU MAXIMUM

temperature alarm

(SET÷110°C; SET÷230°F) when this

temperature is reached the alarm is

enabled, after the “ALd” delay time

Pr2

ALL~ 302

38

50

50

ALL Minimum

temperature alarm

-50.0 ÷ SET°C; -58÷230°F when this

temperature is reached the alarm is

enabled, after the “ALd” delay time

Pr2

-58~ ALu

-25

15

30

ALARM SIGNALS

Message

Cause

Outputs

“P1”

Room probe

failure

Compressor output

according to par. “Con” and

“COF”

“P2”

Evaporator probe

failure

Defrost end is timed

“HA”

Maximum

temperature alarm

Outputs unchanged.

Message

Cause

Outputs

“LA”

Minimum

temperature alarm

Outputs unchanged.

“dA”

Door open

Compressor and fans

restarts

“EA”

External alarm

Output unchanged.