6. Water Supply and Drain Connections
See Fig. 3

• External filters, strainers or softeners may be required depending on the water

quality.

• Water supply inlet is 1/2" female pipe thread (FPT).

• A water supply line shut-off valve and drain valve should be installed. A minimum of
3/8" OD copper tubing is recommended for the water supply lines.

• Water supply pressure should be a minimum of 10 PSIG and a maximum of 113 PSIG. If

the pressure exceeds 113 PSIG, the use of a pressure reducing valve is required.

• Drain outlet for icemaking is 3/4" FPT. The icemaker drain piping connection must be made

separately from the bin drain.

• The drains must have 1/4" fall per foot on horizontal runs to get a good flow.

• The drains should not be piped directly to the sewer system. An air gap of a minimum of

2 vertical inches should be between the end of the drain pipe from the icemaker or the ice
bin and the floor drain.

• A plumbing permit and services of a licensed plumber may be required in some areas.