System Defaults

Table 2. System Defaults

PARAMETERS

CODE

AIR

ELECTRIC

Refrigerant

rEF

R-22

R-404A

Box Temperature

bot

35

°

F

-10

°

F

Superheat

SUP

8

°

F

8

°

F

Slave Evaporator

SLA

No

No

No. of Defrost per Day

dFn

2

4

Defrost Fail-safe time

dFF

40 min.

30 min.

Defrost End Temperature

dFt

45

°

F

60

°

F

Defrost Delay Start Time

dFS

0 hrs.

0 hrs.

Alarm High Temperature

ALH

50

°

F

5

°

F

Alarm Low Temperature

ALL

30

°

F

-15

°

F

Alarm Time

ALt

60 min.

60 min.

Temperature Units

F-C

°

F

°

F

Table 1. Resistance/Temperature Specification

Temperature

°

F

Ohms

Temperature

°

F

Ohms

104

5,320

32

32,650

86

8,060

23

42,330

77

10,000

14

55,330

68

12,490

5

72,950

59

15,710

-4

97,070

50

19,900

-13

130,410

41

25,400

-22

176,960