beautypg.com

Brazing – Hoshizaki F-450MAH User Manual

Page 36

background image

36

2. Brazing

WARNING

1. Refrigerant R-404A itself is not flammable at atmospheric pressure and

temperatures up to 176°F.

2. Refrigerant R-404A itself is not explosive or poisonous. However, when

exposed to high temperatures (open flames) R-404A can be
decomposed to form hydrofluoric acid and carbonyl fluoride both of
which are hazardous.

3. Always recover the refrigerant and store it in an approved container. Do

not discharge the refrigerant into the atmosphere.

4. Do not use silver alloy or copper alloy containing arsenic.

5. Do not use R-404A as a mixture with pressurized air for leak testing.

Refrigerant leaks can be detected by charging the unit with a little
refrigerant, raising the pressure with nitrogen and using an electronic
leak detector.

Note: All brazing-connections are clear-paint coated. Sandpaper the brazing-connec
tions before unbrazing the components. Use a good abrasive cloth to remove
coating.

6) A liquid charge is recommended for charging an R-404A system. Invert the service

cylinder. Open the high-side, service manifold valve.

7) Allow the system to charge with liquid until the pressures balance.

8) If necessary, add any remaining charge to the system through the low-side. Use a

throttling valve or liquid dispensing device to add the remaining liquid charge
through the low-side access port with the unit running.

9) Close the two refrigerant access valves, and disconnect the hoses and service

manifold.

10) Cap the access valves to prevent a possible leak.