Henny Penny CBC/CBR-104 EN User Manual

Page 17

background image

Model CBC/CBR-103,104,105,106,107

3-5. PROGRAMMING

dS: (defrost system (computation)) dF=digifrost feature;

Continued

defrost start time based on total compressor running time.
rt=real time; defrost start frequency, based on real time

dI: (defrost interval) defrost frequency in hours, based on the

selection of “dS”

dE: (defrost endurance) total (maximum) length of a defrost

cycle, expressed in minutes. (1...99 range)

dL: (display lock) temperature display is locked during a

defrost cycle. (0...31 range)
“n”=no (readout continues to display the actual tempera-
ture, even during a defrost cycle
“y”=yes (readout is locked)

dr: (display read-out) select the type of visualization in case of

temperature display lock during defrost (see prameter dL)
“C”=the temperature displayed at the start of a defrost is

locked and does not change during this cycle

“dF”=during the defrost “dF” is displayed

do: (defrost at power on) selects whether or not, the system

goes through the defrost cycle at start-up (or after power
failure)
“n”=no
“y”=yes

dd: (defrost delay at power on) delay of defrost cycle, in

minutes. (0...99 range)

Error Code “E1”

This is the only error code in these controls. It indicates a tempera-
ture sensor failure, such as, a shorted sensor, a sensor break, or
absence of sensor.

It can also indicate an under-range in the system temperature (-55).

In case of an over-range in the system temperature, “99” shows first
in the display, followed by “E1”.