Safety precautions – haier AD42NAMBEA User Manual

Page 6

background image

5

2. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent

or a similar qualified person.

3. If the fuse on PC board is broken please change it with the type of

T 3.15A /250VAC.

4. The wiring method should be in line with the local wiring standard.

1. Applicable ambient temperature range:

The machine is adaptive in following situation

5. The power cable and connecting cable should be self-provided. The power cable should be:

H07RN-F 5G 2.5mm

2

(AD42NAMBEA AD36NAMBEA AD28NAMBEA(380-400V,

3N~, 50Hz)) ;

H05RN-F 3G 4.0mm

2

(AD28NAMBEA AD242AMBE AD242AMERA(1PH,220-230V~,

50Hz))

H05RN-F 3G 2.5mm

2

(AD182AMBEA AD142AMBE (1PH,220-230V~,50Hz).

The connecting cable should be H05RN-F 4G 0.75mm

2

All the cables shall have got the European authentication certificate. During installation,

when the connecting cables break off, it must be assured that the grouding wire is the last one

to be broken off.

6. The power cable and connect cable should be self-provided.

7. The breaker of the air conditioner should be all-pole switch; and the distance between its

two contacts should be no less 3mm.

8. The indoor unit installation height is at least 2.5m.

9. A leakage breaker must be installed.

Safety Precautions

Cooling

Heating

Indoor

outdoor

Rated Maximum Minimum
27 32 18
19 23 14
35 43 10
24 26 6
20 27 15
15 -- --
7 24 -7
6 18 --

DB C
WB C
DB C
WB C

Indoor

outdoor

DB C
WB C

DB C
WB C