18

5. Electric wiring

WARNING

DANGER OF BODILY INJURY OR DEATH

TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE
MAKING ANY ELECTRIC CONNECTIONS. GROUND CONNECTIONS MUST BE
COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS.

(1) Selection of size of power supply and interconnecting wires.

Precautions for Electric wiring

Electric wiring work should be conducted only by authorized personnel.
Do not connect more than three wires to the terminal block. Always use round type crimped terminal
lugs with insulated grip on the ends of the wires.
Use copper conductor only.

Select wire sizes and circuit protection from table below. (This table shows 20 m length wires with
less than 2% voltage drop.)

(2) Wiring connection

Make wiring to supply power to the outdoor unit, so that the power for the indoor unit is supplied by
terminals.

30mA

Item

Model

Phase

3

Switch breaker

(A)

Circuit breaker

Overcurrent protector

rated capacity (A)

Power source

wire size

(minimum)

30

20

4.0mm

2

1

40

26

2.5mm

2

Switch

breaker

Earth leakage breaker

Leak

current

30

30mA

40

AD28NAMBEA

AD36NAMBEA
AD42NAMBEA

AD242AMBEA
AD242AMERA

AD28NAMBEA
AD36NAMBEA
AD42NAMBEA

Installation Manual For Indoor Unit

AD182AMBEA

30mA

1

40

26

4.0mm

2

40

OUTDOOR UNIT
TERMINAL BLOCK

INDOOR UNIT
TERMINAL BLOCK

POWER SUPPLY: 380-400V,3N~,50Hz

R S T

N 1 2 3

1 2 3

Y/G

Y/G

AD242AMBEA AD242AMERA

1 2 3 N L

1 2 3

POWER SUPPLY: 1PH,220-230V~,50Hz

INDOOR UNIT
TERMINAL BLOCK

OUTDOOR UNIT

TERMINAL BLOCK

L N

1 2 3

Y/G

INDOOR UNIT
TERMINAL BLOCK

POWER

1PH,220-230V~,50Hz

SUPPLY:

Y/G

1 2 3

OUTDOOR UNIT

TERMINAL BLOCK

AD182AMBEA