15

Code

Parameter Name

Min Max Units

Setpoint

°C/°F

PS

Password

0

199

/C

Offset for air temp sensor

-127 127 °C/°F

(in tenths of a degree: i.e. a value of “1” adds 0.1° to value)

rd

Regulator differential (superheat) set point (a “0” in this field = 0.5°C or 0.5°F)

0

19 °C/°F

dI

Time between defrost cycles (defrost interval)

0

199 hours

dt

Defrost temperature termination set point

-50

127 °C/°F

dP

Max duration of defrost if using electric or hot gas defrost, or the actual

1

199

min

duration of defrost if doing timed defrost

dd

Drip time

0

15

min

d8

Alarm delay after defrost

0

15

hours

d/

Defrost probe reading (read-only)

°C/°F

AL

Low temperature alarm differential (subtract this value from the temperature

0

127 °C/°F

set point to get low alarm temperature set point) (0 = no low temp alarming)

AH

High temperature alarm differential (add this value to the temperature set

0

127 °C/°F

point to get high alarm temperature set point) (0 = no high temp alarming)

F1

Fan on at temperature set point (used if F0 = 1)

-50

199 °C/°F

Fd

Fan delay after defrost drip time for each F0 value

0

15

min

H5

ID code for programming key

-99

+

T

External parameter programming

-99

199

User Level Setpoints - O5DMA

O5DMA

38
22

0

3
6

44
42

0
1

-10

20

5
1
8