Hill Phoenix 05DMA User Manual
Page 19

15
Code
Parameter Name
Min Max Units
Setpoint
°C/°F
PS
Password
0
199
/C
Offset for air temp sensor
-127 127 °C/°F
(in tenths of a degree: i.e. a value of “1” adds 0.1° to value)
rd
Regulator differential (superheat) set point (a “0” in this field = 0.5°C or 0.5°F)
0
19 °C/°F
dI
Time between defrost cycles (defrost interval)
0
199 hours
dt
Defrost temperature termination set point
-50
127 °C/°F
dP
Max duration of defrost if using electric or hot gas defrost, or the actual
1
199
min
duration of defrost if doing timed defrost
dd
Drip time
0
15
min
d8
Alarm delay after defrost
0
15
hours
d/
Defrost probe reading (read-only)
°C/°F
AL
Low temperature alarm differential (subtract this value from the temperature
0
127 °C/°F
set point to get low alarm temperature set point) (0 = no low temp alarming)
AH
High temperature alarm differential (add this value to the temperature set
0
127 °C/°F
point to get high alarm temperature set point) (0 = no high temp alarming)
F1
Fan on at temperature set point (used if F0 = 1)
-50
199 °C/°F
Fd
Fan delay after defrost drip time for each F0 value
0
15
min
H5
ID code for programming key
-99
+
T
External parameter programming
-99
199
User Level Setpoints - O5DMA
O5DMA
38
22
0
3
6
44
42
0
1
-10
20
5
1
8