beautypg.com

Programming and reviewing settings and changes -13, Program review button select button enter button, Programming & reviewing – Heatcraft Refrigeration Products H-IM-79B User Manual

Page 12

background image

1 2

PROGRAMMING AND REVIEWING SETTINGS/CHANGES

The

Program Review

button is used to program, review and change all program settings

for the system.

Press

“PROGRAM REVIEW”

button. The Setpoint item will appear on the LED. After a few

seconds delay the Setpoint value will display. Each time the button is pressed a different
setpoint item is displayed.

Next, use the

“SELECT”

knob to change value of Setpoint Item.

Next, When the desired value is selected, press the

“ENTER”

button to place it in program

memory. If the

“ENTER”

button is not pressed the value will not be stored in the memory

and thus will not be changed.

“PROGRAM REVIEW” ITEMS

A-E

-

Set Defrost type (

Air

or

ELE

)

rEF

-

Set Refrigerant type (R22, R404A or R507)

bot

-

Set Box temperature (-30°F to +70°F)

SUP

-

Set Superheat (4°F to 20°F)

SLA

-

Set Board as a Slave (Yes or No)

dFn

-

Set Number of defrosts per day (1,2,3,4,5,6,8,10 or 12 per day)

dFF

-

Set Defrost Fail-safe time (10 to 200 minutes)

dFt

-

Set Defrost End temperature (40°F to 100°F)

dFS

-

Set Defrost Delay Start Time (0.5 Hours to 23.5 Hours)

ALH

-

Set Alarm High temperature (-40°F to 90°F)

ALL

-

Set Alarm Low temperature (-40°F to 90°F)

ALt

-

Set Alarm time (2 to 120 minutes)

F-C

-

Set Fahrenheit/Celsius temperature units (°F/°C)

Programming & Reviewing