beautypg.com

Extension cords, Symbology, Safet y op era tion m aintenan c e setu p – Harbor Freight Tools Drillmaster Palm Sander 98622 User Manual

Page 7

background image

Page 7

For technical questions, please call 1-800-444-3353.

Item 98622

SAFET

y

Op

ERA

TION

M

AINTENAN

c

E

SETU

p

Extension cords

1. Grounded tools require a three wire extension cord.

Double Insulated tools can use either

a two or three wire extension cord.

2. As the distance from the supply outlet increases,

you must use a heavier gauge extension cord.

Using extension cords with inadequately sized wire

causes a serious drop in voltage, resulting in loss of

power and possible tool damage.

(See Table A.)

3. The smaller the gauge number of the wire, the

greater the capacity of the cord. For example,

a 14 gauge cord can carry a higher current

than a 16 gauge cord.

(See Table A.)

4. When using more than one extension cord to make

up the total length, make sure each cord contains at

least the minimum wire size required.

(See Table A.)

5. If you are using one extension cord for more

than one tool, add the nameplate

amperes

and use the sum to determine the required

minimum cord size.

(See Table A.)

6. If you are using an extension cord outdoors, make

sure it is marked with the suffix “W-A” (“W” in

Canada) to indicate it is acceptable for outdoor use.

7. Make sure the extension cord is properly wired

and in good electrical condition. Always replace

a damaged extension cord or have it repaired

by a qualified electrician before using it.

8. Protect the extension cords from sharp objects,

excessive heat, and damp or wet areas.

TABLE A: REcOMMENDED MINIMUM WIRE

GAUGE FOR EXTENSION cORDS* (120/240 VOLT)

NAMEpLATE

AMpERES

(at full load)

EXTENSION cORD

LENGTH

25´ 50´ 75´ 100´ 150´

0 – 2.0

18

18

18

18

16

2.1 – 3.4

18

18

18

16

14

3.5 – 5.0

18

18

16

14

12

5.1 – 7.0

18

16

14

12

12

7.1 – 12.0

18

14

12

10

-

12.1 – 16.0

14

12

10

-

-

16.1 – 20.0

12

10

-

-

-

* Based on limiting the line voltage drop to five volts at

150% of the rated amperes.

Symbology

Double Insulated

Canadian Standards Association

Underwriters Laboratories, Inc.

Edison Testing Labs

V

Volts

~

Alternating Current

A

Amperes

n0 xxxx/min.

No Load Revolutions per Minute (RPM)

WARNING marking concerning Risk

of Eye Injury. Wear ANSI-approved

safety goggles with side shields.

Read the manual before

set-up and/or use.

WARNING marking

concerning Risk of Fire.

Do not cover ventilation ducts.

Keep flammable objects away.

WARNING marking concerning

Risk of Electric Shock.

Properly connect power cord

to appropriate outlet.