Ram diagnostic (ramtst), Check of the electrically eraseable prom (seetst), Verification of valid calibration values (caltst) – Honeywell s HercuLine 2000 User Manual
Page 8

62-86-25-14
February 2007
Page 8 of 10
Quick Start Guide for Herculine 2000 Series
Group
Prompt
Function
Prompt
Value or
Selection
Factory
Setting
RELAYn
RTYP
NONE
RnyE
X1
RnyVAL
0.0
RnyHL
LO
RLYnHY
0.0
CU OUT
CUROUT
NONE
Depends on
MSG
COMM
COMM
DIS
ADDRES
1
BAUD
19.2
XmtDLY
20ms
DBLBYT
FP
B
DIGINP
DIGINP
NONE
EndPos
0
DISPLA
DECMAL
8888
EUNITS
PCNT
UNITS
ENGL
LOCK
LOCKID
0
LOCK
NONE
MAENAB
ENAB
STATUS
FAILSF
Read Only
Read Only
RAMTST
Read Only
Read Only
SEETST
Read Only
Read Only
CFGTST
Read Only
Read Only
CALTST
Read Only
Read Only
DRVINF
VERSON
Read Only
Read Only
SPEED
Read Only
Read Only
POWER
Read Only
Read Only
ROTATE
Read Only
Read Only
TAG
6
alpha
characters
MFGDAT
Read Only
Read Only
LREP
Factory Set
Factory Set
LCAL
Factory Set
Factory Set
REPTYP
Factory Set
Factory Set
Group
Prompt
Function
Prompt
Value or
Selection
Factory
Setting
MAINT
TEMP
NONE
TEMPHI
X1
TEMPLO
0.0
hh:mm:ss
ACST
Read
Only
STARTS
Read
Only
Accumulated
Motor Starts
RnCNT
n=1,2,3,or4
Read Only
Relay Cycle
Counts
REGNn
n= 0 to 9
Read Only
Accumulated
Motor Starts
TOTDEG
Read Only
Total Degrees of
Motor Travel
DATSAV
DIS
PASSWRD
Nnnn
MANRST
NONE
LD
CAL
NONE
LD
CFG
DIS
RESTRT
DIS
7. Start up/Operation
After the actuator is completely installed, wired, and
the preliminary adjustments made, check the
operation of the actuator and controlled device
before placing it in service. Operate the controlled
device and check its direction of travel in response
to an increase of the input signal and make sure it is
correct for the process. Actuators having the
optional auto-manual switch must have the knob set
in the AUTO position.
When power is applied to the actuator, the actuator
electronics performs a diagnostic routine on various
device components. These tests include a:
•
RAM diagnostic (RAMTST),
•
Check of the electrically eraseable PROM
(SEETST),
•
Verification that valid parameter values are
in the actuator configuration (CFGTST),
•
Verification of valid calibration values
(CALTST)
•
Test of the local display and LED indicators
(all display segments and LED indicators
light simultaneously).
The optional local display shows the status of the
diagnostics as they are completed during power up.
TEST DONE is shown on the display when
diagnostics are complete and actuator should be in
AUTO mode.
If the Actuator Motor is “Hunting” (Motor does not
drive to a position and stop) the process control
loop is not tuned correctly. Refer to the Instruction
Manual for your controller on how to tune a loop.