HE420A STEAM POWER HUMIDIFIER

5

68-0192—4

8. Flush the copper tubing to remove any debris that can

cause problems at the float valve.

9. Route the tubing to the humidifier float valve, keeping the

tube away from sharp edges.

10. Connect the remaining end of the tubing to the humidifier

float valve.

11. Open the saddle valve so that the water flows slowly and

gently into the water pan.

SET WATER LEVEL

Adjust the humidifier water level prior to mounting.

1. Set the humidifier reservoir on a level surface.

2. Attach the water feed line and allow the unit to fill until the

float valve shuts off the incoming flow of water. The water

level should be between 2-1/4 in. (57 mm) and 2-1/2 in.

(64 mm) deep. If water level is correct, go to step 4.

3. Adjust the water level in small increments. Raise the

water level by pushing down on the center of the float

arm. Lower the water level by pressing the float down

with one hand and pulling up on the center of the float

arm with the other hand. See Fig. 6.

CAUTION

Flooding Hazard.

Inadequate support of the float arm can lead to

valve seat damage and result in water leakage.

Support the float arm during adjustment.

Fig. 6. Adjust water level.

4. Verify the water level by removing enough water to allow

the float valve to automatically fill and shut off the water.

FINISH MOUNTING AND

PLUMBING HUMIDIFIER

1. Mount humidifier as instructed in the Select Location and

Mount section.

2. Route the tubing to the humidifier float valve.

3. Connect the remaining end of the tubing to the humidifier

float valve.

4. Open the saddle valve so that the water flows slowly into

the water pan.

5. Check the compression fittings at the saddle valve and

the float valve. Tighten the fitting slightly to stop any

leakage.

IMPORTANT

Keep all drain lines away from sharp edges.

6. Connect the overflow provision of the humidifier to a suit-

able waste drain.

NOTE: A 5/8 in. (16 mm) ID garden hose can be easily

attached to the overflow fitting.

7. Support the drain line at several locations to prevent

kinks. Be sure to provide support near any heat source.

8. Use a male 1-1/2 in. NPT fitting (not supplied) to connect

the overflow provision of the humidifier.

INSTALLING THE AUTOMATIC

FLUSHING TIMER

Refer to the “Installation Instructions for the Programmable

Humidifier Automatic Flushing Timer” for complete instruction.

CHECKING THE INSTALLATION

After installation is complete, use the following procedure to

check the humidifier operation:

1. Turn on the humidifier water supply.

2. Be sure the humidifier has power and plug in the humidifier.

3. Turn the Convertible Humidity Control to the Test

position.

4. Check that the furnace blower comes on to circulate the

moist air. The blower may take as long as fifteen minutes

to turn on.

5. Reset the Automatic Humidity Control to the desired dial

setting for automatic operation.

OPERATING THE HUMIDIFIER

The Honeywell HE420A Humidifier is controlled by an

Automatic Humidity Control. The Automatic Humidity Control is

mounted in the return air duct where it can be exposed to the

air stream of the return air, and is designed to automatically

adjust the humidity level based on indoor temperature and

humidity, inferred or measured outdoor temperature, and the

dial setting. The control allows for variations in furnace size,

window insulation and average daily climate temperature.

The Automatic Humidity Control requires an initial adjustment

period. Set the frost factor dial on 5 and use Table 2 to adjust

the dial–only one setting at a time–increasing the dial setting if

you feel you need more humidity, or reducing the setting if you

see moisture on the inside of your windows. For more precise

humidity adjustment, set the dial between dial settings. Allow

two days for the humidity level to subside before making

further adjustments. Once you have tuned in the proper

setting, you should not have to further adjust it again. The

control takes over and makes any future adjustments caused

by varying outdoor temperatures, thus reducing moisture

buildup on windows while maintaining the optimal humidity

level.

The Automatic Humidity Control can also be set for manual

operation. Once the control is installed in the cold air return

and internally set to MANUAL, turn the dial to the expected

outdoor temperature. The corresponding optimal humidity level

has been calibrated for you. For example, by setting the dial to

TO RAISE WATER LEVEL

PUSH
DOWN

TO LOWER WATER LEVEL

HOLD
DOWN

PUSH
UP