Requirements, Chimney requirements, Sidewalls/surrounds – Hearth and Home Technologies E39 User Manual
Page 12: E. chimney requirements
12
17335 Rev L
07/04
E36/39/42 INSTALLATION INSTRUCTIONS
Figure 6 - Sidewalls and Surrounds
E. CHIMNEY REQUIREMENTS
When planning your fireplace location, the chimney construction and necessary clearances must be considered. The
fireplace system and chimney components have been tested to provide flexibility in construction. The following figures
are the minimum distances from the base of the fireplace.
1.
Minimum overall straight height
13 ft
2.
Minimum height with offset/return
14.5 ft
3.
Maximum height
90 ft
4.
Maximum chimney length between an offset and return
12 ft
5.
Maximum distance between chimney stabilizers
35 ft
6.
Double offset/return minimum height
20 ft
7.
Maximum unsupported chimney length between the offset and return
6 ft
8.
Maximum straight unsupported chimney height above the fireplace
35 ft
3. Sidewalls/Surrounds
Adjacent combustible side walls must be located a minimum of 12 in. from the fireplace opening. See Figure 6. If
you are using a decorative surround constructed of combustible material, it must be located within the shaded area
defined in Figure 6. Short stub walls are also acceptable if they are contained within the shaded area.
Cat #
A
B
E/EC36
36 in. - 914 mm
41 in. - 1041 mm
E/EC39
39 in. - 991 mm
44 in. - 1118 mm
E/EC42
42 in. - 1067 mm
47 in. - 1194 mm