CAUTION:
FAILURE TO INSTALL THE VENT PLUG CAN CAUSE PREM ATURE FAILURE OF THE
REDUCER SEALS AFTER EXTENDED USE AND VOID YOUR W ARRANTY.
6. Mount the reversing switches in a suitable location protected from water and near enough to each other to allow for
easy operation.
7. Assemble safety latches to ends of hooks. Attach hooks to plain double blocks with shackles.
8. Attach pulley blocks to all hangers as shown in diagram.
9. Reeve the wire rope through the blocks and spools as shown. Be careful to wind the rope in tight, even layers on the
spools. If the wire rope is wound properly from the beginning it will not kink or break the wire strands. Secure cable
ends with wire rope clamps.
10. Attach the slings or I-beam cradles to the lifting blocks per their instruction.
11. Refer to Power Supply Connections Section Before Proceeding.
12. Pull the boat into the lift and raise it up slowly. If one corner tightens before the others, lower the boat.
13. Slide some wire rope through the loop in the spool from the loose corner toward the tight one to level the boat. If the
blocks twist on themselves when unhooked, loosen the cable clamps at the block and unwind the wire rope until the
block hangs straight. Retighten the clamps.
POWER SUPPLY CONNECTIONS
1. Insure power supply is compatible with motor nameplate ratings. The motor must be connected to a properly rated
branch circuit to help minimize voltage drops during operation.
WARNING:
THE POWER DRIVE AND SUPPLY LINE M UST BE INSTALLED AND INSPECTED BY A
CERTIFIED ELECTRICIAN IN ACCORDANCE WITH LOCAL ELECTRICAL CODES.
BECAUSE WATER AND ELECTRICITY ARE POTENTIAL SAFETY HAZARDS, THIS
INSTALLATION M UST INCLUDE A PROPERLY WORKING GROUND FAULT CIRCUIT
INTERRUPTER. (G.F.C.I.)
Use the following wire sizing guide in wiring the power drive.
WIRE SIZING GUIDE
FOR REFERENCE ONLY
Distance Î
Motor amps
Ð
50 feet
100 feet
150 feet
200 feet
250 feet
300 feet
350 feet
400 feet
5 amp
#12 awg
#12 awg
#10 awg
#10 awg
#8 awg
#8 awg
#6 awg
#6 awg
7.5 amp
#12 awg
#12 awg
#10 awg
#10 awg
#8 awg
#8 awg
#6 awg
#6 awg
10 amp
#12 awg
#10 awg
#10 awg
#8 awg
#8 awg
#6 awg
#6 awg
#4 awg
12.5 amp
#12 awg
#10 awg
#10 awg
#8 awg
#8 awg
#6 awg
#6 awg
#4 awg
15 amp
#10 awg
#10 awg
#8 awg
#8 awg
#6 awg
#6 awg
#4 awg
#4 awg
17.5 amp
#10 awg
#10 awg
#8 awg
#8 awg
#6 awg
#6 awg
#4 awg
#4 awg
20 amp
#10 awg
#8 awg
#8 awg
#6 awg
#6 awg
#4 awg
#4 awg
#2 awg
22.5 amp
#10 awg
#8 awg
#8 awg
#6 awg
#6 awg
#4 awg
#4 awg
#2 awg
25 amp
#8 awg
#8 awg
#6 awg
#6 awg
#4 awg
#4 awg
#2 awg
#2 awg
Awg. - American Wire Gauge Amp. - Motor Full Load Current Feet - Distance From MAIN Breaker Box to Ctrl Panel