V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATOR

60-2309—1

3

6

Fig. 3. 7616BR Damper Crank Arm can be attached to

actuator shaft to drive a damper when valve is open.

WIRING

WARNING

Electrical Shock Hazard.

Can cause serious injury or death.

Disconnect power supply before making wiring

connections to prevent electrical shock and equipment

damage.

Wiring must comply with all applicable electrical codes,

ordinances and regulations. Wiring to the actuator must be

NEC Class 1.

Connect the power supply to terminals 1 and 2 on the V4055

terminal strip. Refer to Fig. 4 for Auxiliary Switch connections

and Fig. 5 for Max Flow Limit Switch connections. For typical

system hookups, refer to Fig. 6 and to instructions packed with

the device used to control the valve.

When all wiring connections are complete, replace the actuator

faceplate.

CAUTION

Operation Hazard.

Improper wiring can cause improper and

dangerous operation.

Label all wires prior to disconnection when servicing

valves. Wiring errors can cause improper and

dangerous operation.

NOTE: Pipe sealant is required on the conduit threads of

actuators with NEMA 4 enclosures.

Adjust Auxiliary Switch (If Used)

The Auxiliary Switch is adjustable throughout the stroke of

the actuator. With the switch installed in the actuator, turn

the adjusting screw (see Fig. 2) clockwise

to cause the

switch to operate earlier in the stroke or counter-

clockwise

to cause the switch to operate later in the

stroke.

Fig. 4. External connections to the V4055 Actuator.

Fig. 5. Connecting the Max Flow

Limit Switch to the actuator.

NOTE: The Proof-of-Closure Switch is not adjustable.

Adjust Max Flow Limit Switch (If
Used)

The Max Flow Limit Switch is adjustable throughout the stroke

of the actuator. With the switch installed in the actuator, turn

the adjusting screw clockwise

to cause the switch to

operate earlier in the stroke or counter-clockwise

to

cause the switch to operate later in the stroke.

52 DEGREE
ANGULAR
ROTATION

MAXIMUM
TRAVEL

SHAFT

7616BR
DAMPER
ARM

M7322

RADIUS

2-11/16 (68.3)

2-5/16 (58.7)

1

2

3

2

1

1

2

AUXILIARY
SWITCH

L1
HOT

L2

POWER SUPPLY. PROVIDE OVERLOAD PROTECTION AND
DISCONNECT MEANS AS REQUIRED.

SWITCH BETWEEN THESE TWO LEADS IS CLOSED WHEN
VALVE IS SHUT (DE-ENERGIZED).

3

SWITCH BETWEEN THESE TWO LEADS IS OPEN WHEN
VALVE IS SHUT (DE-ENERGIZED).

NO

NC

C

NO

NC

C

PROOF-OF-CLOSURE
SWITCH

2

3

M7334

M12798

C

7800 SERIES
RELAY
MODULE

NC

NO

ADJUSTABLE
MAX
FLOW
LIMIT
SWITCH

FIELD WIRING
INTERNAL WIRING

TRAVEL
LIMIT
SWITCH

PUMP
MOTOR

PUMP
VALVE

1

L2

9

2

3

4