EATON CORPORATION Eaton 9390 Uninterruptible Power System

Integrated
Accessory
Cabinets for
customizable
configurations

Eaton offers several configura-
tions of Integrated Accessory
Cabinets (IAC) for use with the
9390 UPS. Major functions of
the IAC include: maintenance
bypass, parallel tie capability and
power distribution with combi-
nations up to (2) 42-pole panel-
boards and (6) sub-feed breakers
per IAC.

The IAC is primarily available in
two forms – either a 200 mm
(8”) sidecar bolted to the UPS
(maintenance bypass or tie) or
a 570 mm (22.5”) free-standing
cabinet (maintenance bypass, tie
or distribution). The size of the
IAC is primarily dependant on
function and rating.

IAC-SB and IAC-B
Maintenance bypass

Maintenance bypass configura-
tion (MBP) and maintenance
isolation (MIS) breakers enable
power to completely bypass the
UPS power module. The module
can then be serviced safely or
replaced without interrupting
power to critical systems. An
optional bypass breaker (BIB)
and rectifier input breaker (RIB)
provide a single wiring point
input to the UPS as well as a
convenient method for removing
power from the UPS when using
maintenance bypass to supply
the load.

Features

• Line and match design

• Two, three or four-breaker

maintenance bypass

• No internal transformers

• Smallest cabinet ships bolted

to UPS (IAC-SB)

• Large cabinet can be remote-

ly located (IAC-B)

IAC-ST and IAC-T
Tie Cabinet

• Parallel UPS tie cabinet

(redundant). See one-line
diagram on next page.

• Two-breaker tie with mainte-

nance bypass (IAC-T only)

• Two-breaker tie-with

main output

• Two-breaker tie

• Wall-mounted maintenance

bypass, tie and distribution
panels are also available

IAC-B Maintenance
bypass (160 kVA)

Rectifier input
(not shown)

Bypass input

Bypass breaker

UPS output
(isolation)

System load
breaker (SLB)

UPS #2 output
(MOB 2)

UPS #1 output
(MOB 1)

IAC-T Parallel Tie Cabinet

8”

22.5”

160 kVA 208V

IAC-B

80 kVA 208 &

480V

160 kVA 480V

IAC-SC

IAC-D Distribution
Cabinet

• Used to add (2) additional

42-pole panelboards

Or

• (1) 42-pole panelboards and

up to (3) 250A distribution
breakers

Or

• Up to (6) 250A distribution

breakers

• Line and match or remote

• Casters and leveling feet

• Panelboards come with indi-

vidual 225A main breaker

• Neutral rated for harmonic

loads (200%)

• Distribution breakers are

Eaton JG electronic trip
- Two electronic sensors
available 100A and 250A
- 100A settings 40-100A trip
(eight

settings)

- 250A setting 100-250A trip
(eight

settings)