Product Data Document

420DS-6d /

D301311X012

June 2011 - Page 4

ControlWave

®

Express

Remote Automation Solutions

Website: www.EmersonProcess.com/Remote

ControlWave Express Process I/O

ControlWave Express I/O module is designed to

maximize usability while minimizing installation and

maintenance.

The I/O module (bottom card) provides a mix of

analog and digital inputs and outputs that are a

perfect fit for small RTU applications.

2 DI/PI (on CPU)

1 RTD input on 14 MHz CPU

4 DI

2 DO

2 selectable DI or DO

2 selectable DI or HSC

Optional 3 AI or 3 AI and 1 AO

Features

Convenient pluggable local terminations

All configuration jumpers and switches

accessible without disassembly of circuit boards
Termination points for external loop power

supply

Specifications

All I/O

I/O access: 50 ms with 33 MHz CPU, 250 ms

with 14 MHz CPU

1 second for 2 DI/PI inputs on CPU board

Surge protection: Meets C37.90-1978

30 Vdc transorb between signal and ground

Terminations are pluggable and accept a

maximum wire size of 16 gauge
Power consumption is stated for each I/O

module type measured at the input supply and

does not include loop power

Pulse/Digital Inputs

Inputs located on base CPU board

Number of points: up to 2 non-interrupting

inputs
Internally sourced, dry contact single ended

inputs
Scan rate: Once per second

Input filter: 20 microSec

Voltage Range: Internally sourced dry contact

input - 3.3 Vdc
On state: >1.6 V, Off state <1.3V

Input current : 200 µA for low power applications

Power consumption:

200 µA input, all inputs ON: 0.002 watt
Used as Pulse Input:
Frequency Range: 0-10 kHz

Debounce: None

Accumulator: 16 bit

RTD Input

Input available on 14 MHz Ultra Low Power

CPU only

Specifications are for the interface only, not includ-

ing the RTD probe or wiring

RTD Conversion Accuracy: ± 0.1°C, or ± 0.1%

of reading, whichever is greater