beautypg.com

Specifications, Lm series surge suppression, Ul 1449 clamping data – Emerson Liebert LM Series User Manual

Page 4: Chart b – lm series dimensional data, Life cycle surge testing, Emi/rfi noise rejection chart a – example

background image

S

C

Specifications

4

RED

LINE

DOES

NOT

PRINT

-USE

AS

GUIDE

FOR

TRIMMING-PLEASE

REMOVE BEFORE

PRINTING

LM

2 5 0

1 2 0

Y

A

R

C

E

Maximum Continuous

Operating Voltage (MCOV)

120V ±25%, all others ±15%

Fault Current Rating (AIC)

200 kAIC

Operating Frequency Range

47 - 63 Hz

Response Time

< 0.5 nanoseconds

Operating Humidity

0% to 95%

Status Indication

LEDs, Dry Contacts, Audible Alarm

Certifications

UL 1449 & 1283, CUL, NEMA LS1, ISO 9001

Enclosure

NEMA 12

Warranty

5 Years Parts

LM Series Surge Suppression

System Voltage

L-N

L-G

L-L

N-G

120/208

400

400

700

400

120/240

400

400

700

400

346/600

1200

1200

2000

1200

277/480

700

700

1500

700

480

X

1500

1500

X

600

X

1800

2000

X

UL 1449 Clamping Data

(Second Edition)

Dimensions (inches)

Approx. Weight

Unit

Options

A

B

C

D

E

F

LM060
LM080

All

16

14

8

16.75

12.0

0.31

35

LM100
LM125
LM150

LM200
LM225

All

20

16

9

21.25

10

0.31

45

LM250

Chart B – LM Series Dimensional Data

How To Specify The Appropriate Model:

All LM model numbers begin with a LM prefix. Use Chart A to build your LM starting with the Surge Rating column. Moving left to right,

choose the correct configurations from each column for your application. Your completed model number should look similar to the example

below or LM250120YARCE. Refer to Chart B for LM Series dimensional data.

Standard Monitoring

System, LEDs,

Audible Alarm,

Dual Form C

Contacts

LEDs, Audible

Alarm, Surge

Counter, Dual

Form C Contacts

E

R

T

X

NEMA 12 (Standard)

NEMA 3R

NEMA 4

NEMA 4X

Unit

Per Mode

Per Phase

060-080

8,000

16,000

100-150

16,000

32,000

200-250

24,000

48,000

Life Cycle Surge Testing

10kA, 20kV, IEEE, Cat. C3

Single Unit

Frequency

System Installation

34dB

100kHz

51dB

51dB

1MHz

94dB

54dB

10MHz

114dB

48dB

100MHz

120dB

EMI/RFI Noise Rejection

Chart A – Example

Model#

Indicators

L

o

w C

o

s

t

M

odul

ar

L

M

Surge Rating

60kA/mode

060

80kA/mode

080

100kA/mode 100

125kA/mode 125

150kA/mode 150

200kA/mode 200

225kA/mode 225

250kA/mode 250

L - G Voltage

120-120V

208-208V

220-220V

230-230V

240-240V

277-277V

480-480V

600-600V

Configuration

Single Phase L-N, 2W+gnd

N

Single Phase L-L, 2W+gnd

L

Split Phase, 3W+gnd

S

Three Phase Wye 4W+gnd

Y

Three Phase Delta 3W+gnd

D

Three Phase Delta Hi-leg 3W+gnd

H

Modes of

Protection

ALL

A

Connection

Options

WireLug N

Disconnect R

Enclosure

Monitoring Options