beautypg.com

Specifications, Ul 1449 ratings, Surge current capacity – Emerson PanelGuard 65 User Manual

Page 2: Enclosure, Emi/rfi noise rejection values, How to order liebert liebert panelguard, Extension

background image

Emerson Network Power.com

Emerson Network Power.

The global leader in enabling

Business-Critical Continuity

.

AC Power

Connectivity

DC Power

Embedded Computing

Embedded Power

Monitoring

Outside Plant

Power Switching & Controls

Precision Cooling

Racks & Integrated Cabinets

Services

Surge Protection

Liebert Corporation

1050 Dearborn Drive

P.O. Box 29186

Columbus, Ohio 43229

800 877 9222 Phone (U.S. &

Canada Only)

614 888 0246 Phone (Outside U.S.)

614 841 6022 FAX

Via Leonardo Da Vinci 8

Zona Industriale Tognana

35028 Piove Di Sacco (PD)

Italy

39 049 9719 111 Phone

39 049 5841 257 FAX

Emerson Network Power Asia Pacific

7/F., Dah Sing Financial Centre

108 Gloucester Rd, Wanchai

Hong Kong

852 25722201 Phone

852 28029250 FAX

liebert.com

Technical Support

800 288 6169 Toll-Free

607 724 2484 Phone

607 722 8713 Fax

UL 1449 RATINGS

Line to Line

to Line

Neutral

System Voltage

Neutral

Ground

to Line

to Ground

120/208 or 120/240

400 V

400 V

800 V

400 V

208, 240, 277 or 277/480

800 V

800 V

1500 V

800 V

Specifications

Surge Current Capacity

Minimum Tested

Single Pulse Surge Current Capacity

Protection Mode

Impulses Per Mode

Model 100

Model 80

Model 65

Line-to-Neutral

> 3,500

> 100,000 A

> 80,000 A

> 65,000 A

Line-to-Ground

> 3,500

> 100,000 A

> 80,000 A

> 65,000 A

Neutral-to-Ground

> 3,500

> 100,000 A

> 80,000 A

> 65,000 A

Line-to-Line

> 3,500

> 100,000 A

> 80,000 A

> 65,000 A

Per Phase

> 7,000

> 200,000 A

> 160,000 A

> 130,000 A

Enclosure

NEMA 1 rated.

Surface mount dimensions are 12” x 20” x 6”.

Flush mount unit is 12” x 21.5” x 6”.

Weight is 15 lbs.

EMI/RFI Noise Rejection Values

Single Unit

Frequency

System Installation

34 dB

100 kHz

51 dB

51 dB

1 MHz

94 dB

54 dB

10 MHz

114 dB

48 dB

100 MHz

120 dB

How To Order Liebert Liebert PanelGuard

Extension

Duty life cycle tested to survive 20kV, 10kA, IEEE C62.41 Category C3 surge current

with less than 5% degradation of clamping voltage.

All systems EMI-RFI noise or attenuation rejection values are in compliance with test

and evaluation procedures outlined in NEMA LS 1-1992, paragraphs 2.2.11 and 3.11.

Phase configuration Code

1 Ph, 3W+G. 120/240 VAC

120S

3 Ph, 4W+G. 120/208 VAC

120Y

3 Ph, 4W+G. 277/480 VAC

277Y

Other phase configurations available.
Please consult factory.

kA per mode/per phase

Code

65 kA per mode, 130 kA per phase

65

80 kA per mode, 160 kA per phase 80

100 kA per mode, 200 kA per phase

100

Trim type

Code

Surface mount trim

S

Flush mount trim

F

Monitoring options

Code

Standard Status LEDs only

-00

LEDs, Audible Alarm, Counter

-01

LEDs, Audible Alarm

-02

LEDs, Counter -03

How to construct a Liebert PanelGuard

Extension (LPGE) model #

Code

1. Liebert PanelGuard Extension

LPGE

2. Phase configuration

120S

3. kA per mode /per phase

65

4. Trim type: surface mount

S

5. Monitoring options -01

Sample model #: LPGE120S65S-01

While every precaution has been taken to ensure accuracy and

completeness in this literature, Liebert Corporation assumes no

responsibility, and disclaims all liability for damages resulting

from use of this information or for any errors or omissions.

© 2008 Liebert Corporation. All rights reserved throughout

the world. Specifications subject to change without notice.

All names referred to are trademarks or registered trademarks

of their respective owners.

® Liebert is a registered trademark of the Liebert Corporation.

SL-22065 (R06/08) Printed in USA

Business-Critical Continuity

, Emerson Network

Power and the Emerson Network Power logo are

trademarks and service marks of Emerson

Electric Co. ©2008 Emerson Electric Co.

800 288 6169 Toll-Free

607 721 8865 Phone

607 722 8713 Fax