beautypg.com

Dvvk-5f flex vent instructions – Empire Comfort Systems DVP48FP3 EN User Manual

Page 42

background image

21759-6-0608

Page 42

INSTALLATION

1. Unpack vent components and check that all items are included.

2. Check to see that the vent spacer springs are located around the

flue vent at 8" and 12" intervals along its length. See Figure 69.

If not, stretch the spacer springs to about 15" long and wrap them

around the flue, then interlock the ends of each spring about 2".

See Figure 70. Maintain equal distance between spring spacers.

3. Use existing 8" dia. inlet collar to attach outer vent pipe.

4. Install the Wall Firestop/Thimble assembly as required through

the wall. Refer to the venting charts in the fireplace manual to

determine the proper height and size of the vent opening. The

minimum opening should be 10" wide by 12" high. The minimum

combustible clearance from the horizontal vent is 1" from sides

and bottom, and 3" above the vent pipe. See Figure 72.

5. In most cases, after determining the length of the vent that is

needed, it may be easier to install the flue and outer vent pipes to

the Termination Cap first, then from the outside, feed the venting

through the wall to the fireplace.

6. If the venting is to long, trim off any excess vent before attaching

the vent end connectors.

7. Attach the Termination Cap to the outside of the house.

8. Prior to making the vent connections, apply high temperature

sealant (1000 degree F min.) to the vent connections before

securing with the band clamps provided. Note: the flue pipe end

without the adapter is to be installed to the Termination Cap.

9. Apply sealant to the outside of the flue pipe adapter and connect

to the flex flue pipe. Then insert the adapter into the fireplace

flue. Secure flue adapter to the fireplace flue with a minimum of

two screws provided. See Figure 71.

10. Attach the Outer Vent pipe to the 8" dia. Collar on the fireplace

with a large band clamp provided. Sealant may also be used on

the outer vent connections.

11. Check all vent connections for tightness. Make sure horizontal

venting has the proper rise and combustible clearances required.

Refer to venting charts in fireplace instruction manual.

FLEX OUTER VENT

FLEX FLUE PIPE

SPACER

SPRINGS

BAND CLAMP

5” DIA. FLUE

ADAPTOR

COLLAR

5” DIA. FLEX

FLUE PIPE

8” DIA. FLEX

VENT PIPE

APPLY HIGH

TEMPERATURE

SEALANT

8” DIA. FIREPLACE

INLET COLLAR

Top of Vent

Combustibles NOT
allowed in shaded
area

1"

1"

3"

(25 mm)

8” Diameter
intake vent

5” Diameter flue

(25 mm)

(76 mm)

• (1) Horizontal Termination Cap

• (1) 4-foot section of Flex vent with spacers (5" flue/8"

outer pipe)

with flue adapter collar

• (1) Wall Firestop/Thimble Assembly

• Hardware pack that includes band clamps and screws

Flex venting can be installed either vertically or horizontally off of the DVP Series fireplaces. When installing a horizontal vent run

from top connections, maintain at least ½" rise for every 12" of vent run. When venting horizontal off the rear vent connections, allow

a minimum rise of 2". Refer to the Figure 68 when mounting termination near vinyl siding.

CAUTION: Always stretch and secure venting with wire or metal strapping to ensure that the horizontal runs do not sag.

If space permits, it is generally easier to attach venting in the top vent configuration.

Because of sharp edges, always use gloves when handling the flex vent components.

Vent connections should overlap a minimum of 1" for proper sealing.

Always follow the general venting requirements for vent terminal location, vent lengths, and clearance to combustible materials.

Figure 69

Figure 71

8”

(203 mm)

8”

(203 mm)

8”

(203 mm)

4” FLEX
VENT PIPE

SPACER
SPRING

The DVVK-5F FLEX VENT KIT includes the following components:

Figure 72

Figure 70

DVVK-5F FLEX VENT INSTRUCTIONS

This manual is related to the following products: