INSTALLATION

Approved Venting Method 3: Internal or External Masonry Chimney System






Please Note:
Installation diagrams are for reference purposes only and are not drawn to scale, nor meant to be used as plans for each individual
installation. Please follow all venting system requirements, maintain the required clearances to combustibles, and follow all local
codes.

Chimney Connector 

(Single or Double Wall) 

3.

0

 ft.

 

2.

0

 ft.

 

10 ft. 

The 10‐3‐2 Rule: The chimney system 
must terminate 3.0 ft. above the point 
where its centerline passes through the 
roof AND the chimney must terminate 
2.0 ft. above any part of the dwelling 
within a 10 ft. radius of the chimney. 

18.

0

 in.

 

Masonry Thimble with 

proper clearance to 

combustibles

Chimney liner cross‐sectional 

area (Length x Width) must be 
no larger than twice the cross‐

sectional area of the flue collar 

(2 x 28.27 in

= 56.55 in

2

).  If 

chimney liner is larger than 

56.55 in

2

, relining with a 5.5” 

or 6.0” liner is required 

Ash Cleanouts must 

have an airtight seal to 

prevent weak draft. 

 Follow the rules listed above concerning maximum permissible flue liner size; installing this unit on masonry 

chimneys exceeding 56.55

 in

2

 in cross‐sectional area will result in decreased draft and the potential for poor unit 

performance.  

 Use three sheet metal screws at each single wall chimney connector joint (check manufacturer’s 

recommendations when double wall chimney connector is used). 

 Drill three holes in the flue collar of the unit and attach the chimney connector to the unit using sheet metal 

screws. 

 Avoid numerous elbows and excessive horizontal runs as both will lead to poor draft and increased creosote 

accumulation.   Horizontal runs of chimney connector must never exceed 4.0 ft. and the overall length of the 
chimney connector must not exceed 8.0 ft. 

 A tight seal at the thimble is crucial for proper unit performance and to create a safe installation.  Use the proper 

adapter designed for connecting single or double wall chimney connector to a masonry thimble. 

 Have existing masonry chimneys inspected for safety and proper clearances to combustibles before putting them 

into service; a qualified chimney sweep can perform this inspection. 

 External masonry chimneys often suffer cold downdrafts and poor draft performance even when they meet the 

cross‐sectional area rules.  In this case, a 6.0” insulated liner may be necessary. 